English
Language : 

F10-1D22-BKB Datasheet, PDF (6/12 Pages) Magnetrol International, Inc. – F10 & F50 Flow Switches
F10 DIMENSIONAL SPECIFICATIONS
INCHES (mm)
NOTE: Model F10s are intended for use in horizontal pipelines only.
For proper performance, a straight pipe run of 12 pipe diameters upstream and
3 pipe diameters downstream of the switch is recommended.
5.93 (150)
3.87 (98)
10.12
(257)
A
5.25
(133)
7.38
(187)
Top of
pipe run
8.46
(214)
A plugged
21/2" ANSI
mounting flange
21/2" ANSI flange
(to match F10)
Standoffs (Qty. 3)
3.00 (76) Diameter
Vane length dependent
upon line size
CONDUIT CONNECTIONS A
Electrical Switches:
TYPE 4X/7/9: 1" NPT
Group B:
1" NPT
Pneumatic Switches:
NEMA 1:
1/4" NPT
All housings rotatable 360°
Note:
Allow the following for overhead
clearance for cover removal:
NEMA 1
TYPE 4X/7/9
Group B
8.00 (203)
10.00 (254)
10.00 (254)
Flow Vane
0.19 (5) Minimum
F10 with flanged connection
1.75
3" Pipe and up
(44)
1.50
(38)
2" and 21/2" Pipe
5.93 (150)
3.87 (98)
Line
Size
2"
21⁄2"
3"
31⁄2"
4"
5"
6"
8"
Over 8"
Dim. B
Max.
1.81 (46)
1.94 (49)
1.88 (48)
1.88 (48)
2.00 (51)
2.06 (52)
2.12 (54)
2.19 (56)
2.31 (59)
Equivalent
Max. Wall
Schedule
80
160
80
80
120
120
120
100
—
6
10.12
(257)
A
FLOW
2.50
(63) B 1.56 (40)
8.46
(214)
A
plugged
2" NPT 3000# Bonney Threadolet
or equal (supplied by customer)
Vane length dependent
upon line size
Pipe line size
(horizontal lines only)
2.56 (62) Dia. .06 (2)
1.75
Vane
(44)
width
1.50
(38)
F10 with 2" NPT connection
3" Pipe and up
2" and 21/2" Pipe