R1J-400I1H2A0 Datasheet, PDF (7/12 Pages) List of Unclassifed Manufacturers – 400W+400W Redundant Power Supply | |||
|
◁ |
SURE STAR
SURE STAR
5. é»æºè¯å¥½ä¿¡è Power good signal
The system shall have an active high TTL compatible signal capable of sinking 1mA and
sourcing 100uA. The signal shall become active within 100 to 500 ms from the instant +5V output
reaches a steady state level within the specified regulation limits. It shall become inactive at least
1 ms before +5V drops to below the lower regulation limit.
Power good @ 115/230VAC , Full Load 200ms ~ 500ms
Power Fail @ 115/230VAC , Full Load 1ms (Min.)
6. ä¿è· Protection
6.1. éå£ä¿è· Over voltage protection
Output
Min
Max
Comments
+3.3V
3.75V
4.3V
PSU shutdown
+5V
5.7V
6.9V
PSU shutdown
+12V
13V
14.3V PSU shutdown
Noteï¼æ該å¨æ大交æµè¼¸å
¥é»å£230ä¼åè¼è¼ã空è¼ä¸æ¸¬è©¦ã
The power supply shall be test at max AC voltage (230Vac) and min load or no load.
6.2. ä½å£ä¿è· Under-voltage protection
Output
Min
Max Comments
+3.3V
2.0V
2.4V PSU shutdown
+5V
3.3V
3.7V PSU shutdown
+12V
8.5V
9.5V PSU shutdown
Noteï¼æ該å¨æ大交æµè¼¸å
¥é»å£230ä¼åè¼è¼ã空è¼ä¸æ¸¬è©¦ã
The power supply shall be test at max AC voltage (230Vac) and min load or no load.
6.3. éæµä¿è· Over current protection
Output Over Current(Type) Over Current(Max.) Comments
+3.3V
â§22A
30A
PSU shutdown
+5V
â§22A
30A
PSU shutdown
+12V
â§35.2A
48A
PSU shutdown
Noteï¼éæµä¿è·æ¸¬è©¦æ¯å¨å
¶ä»é¡å®è² è¼æ測試ã
The over current protection should be tested at other load rating.
â¦
|
▷ |