English
Language : 

ZB2BT4 Datasheet, PDF (2/24 Pages) List of Unclassifed Manufacturers – Push Buttons and Operator Interface
Push Buttons and Operator Interface Specifiers Guide
XB2B 22 mm
General Characteristics
Environment
Conformity to standards
Approvals
Protective treatment
Ambient temperature
Resistance to vibration
Resistance to shock
Protection against electric shock
Degree of protection
conforming to IEC 60529
and NF C 20-010
Mechanical life
XB2B, XD2P: UL 508, IEC 60947-5-1, EN60947-5-1, IEC 60337-1, IEC 60337-2, NF C 63-140, ASE 0119, ASE1003 ,
BS 4794, VDE 0660-200, CSA C 22-2 No. 14, CSA C 22-2 No. 66
UL: push buttons and selector switches NEMA / UL Type A600-Q600;
pilot lights and illuminated push buttons direct supply (120 V max.);
pilot lights and illuminated push buttons with transformer (600 V)
CSA: push buttons and selector switches NEMA / UL Type A600-Q600.
pilot lights and illuminated push buttons direct supply (120 V max.);
pilot lights and illuminated push buttons with transformer (600 V).
ASE, DEMKO, NEMKO, SEMKO, BUREAU VERITAS, SAHKOTARKASTUSKESKUS, GL, DNV, LROS
XD2P, standard version: CSA A600-Q600, LROS.
Standard version: TC “All climates”
Operating: -25 °C to +70 °C (-13 °F to +158 °F) Storage: -40 °C to +70 °C (-40 °F to +158 °F)
60 mm diameter mushroom head: 8 g. Other push buttons: 15 g. Small joystick controllers: 5 g (from 40 to 50 Hz)
Conforming to IEC 60068-2-6.
Push buttons: 70 g. Mushroom head push-buttons: 15 g. Selector switches: 200 g. Conforming to IEC 60068-2-27.
XB2B, XD2P: Class 1, conforming to IEC 60536 and NF C 20-030.
NEMA / UL ratings XB2B: 1, 2, 3, 4, 4X, 12K, 13, XB2B, XD2P: IP 65: flush and protecting, illuminated and non-
illuminated push buttons (mounted). IP 66: booted and mushroom head push buttons, selector switches, pilot lights and
small joystick controllers (mounted). IP 40: double- headed push buttons (IP 65 on request).
Push buttons—3 million operations (Latching mushroom head push buttons: 300,000 operations. Illuminated selector
switches: 100,000 operations). The product life expressed is based on average usage and normal operating conditions.
Actual operating life will vary with conditions. The above statements are not intended to nor shall they create any express
or implied warranties as to product operation or life. For information on the limited warranty offered on this product,
please refer to Square D terms and conditions of sale found in the Square D Digest.
Contact block characteristics
Nominal thermal current
Limited Availability Nominal insulation voltage
Insulation category
Contact operation
For replacement use only. Contact resistance
Operating force
For new applications, use Terminalreferencing
Short circuit protection
XB4 (page 37 - 72) Rated power
10 A conforming to IEC 60947-5-1, NF C 63-140, UL 508, CSA 22-2 No. 14, VDE 0660 part 2, NEMA / UL Type A600-Q600.
500 V conforming to NF C 20-040, VDE 0110, IEC 60158-1, 600 V conforming to UL 508, 600 V conforming to
CSA 22-2 No. 14.
Group C conforming to NF C 20-040 and VDE 0110.
Slow- make N.O. or slow-break N.C. with direct opening operation conforming to EN60947-5-1
section 3.
ð25 m¾ conforming to: NF C 93-050 method A or IEC 60225-7 category 3.
Flush or projecting push buttons - with 1 NO contact: 2.25 lb - with 1 NC contact: 1.8 lb
Additional contacts - N.O.: add 1 lb - N.C.: add 0.7 lb.
Conforming to CENELEC EN 50013.
10 A cartridge fuses, Gl or N conforming to IEC 60269-1and VDE 0660-200.
DC supply
conforming to IEC 60947-5-1 Appendix C
Power broken in watts
duty categories AC11-DC11
for 1 million operations
File E164353
Operating frequency: 3,600 ops/hour
CCN NKCR
Load factor: 0.5
Voltage 24 V 48 V 120 V
®
AC supply (50-60 Hz)
Inductive
load
65 W 48 W 40 W
File LR 44087
127 V
1
220 V 24/48 V
ith = 10 A
06
04
AC Ratings, Inductive - NEMA / UL A600
35% Power factor
Volts
Make
Amperes
VA
Break
Amperes
VA
Continuous
carrying
Amperes
Resistive 75%
Power factor
Make, Break and
continuous
Class 3211 03
Marking
02
Amperes
01
.06
.04
.02
.01
1 2 4 6 10 20 40 60
current in amperes
120
60
7200
6
720
10
240
30
7200
3
720
10
480
15
7200
1.5
720
10
600
12
7200
1.2
720
10
DC Ratings, NEMA / UL Type Q600
Inductive and resistive
Volts
Make and break
125
0.55
10
10
10
10
Continuous
2.5
250
0.27
2.5
600
0.10
2.5
Cabling
XB2B, XD2P: Screw and captive clamp terminals. Recommended torque 15.62 lb-in. Capacity: minimum 1 x 0.5 mm2
(20 AWG) solid or stranded, maximum with or without cable end: 2 x 1.5 mm2 (16 AWG) or 1 x 2.5 mm2 (14 AWG) or by
quick connector conforming to NF C 20-120 (on request).
314
© 1999 - 2000 Schneider Electric All Rights Reserved
11/00
Courtesy of Steven Engineering, Inc. ! 230 Ryan Way, South San Francisco, CA 94080-6370 ! Main Office: (650) 588-9200 ! Outside Local Area: (800) 258-9200 ! www.stevenengineering.com