English
Language : 

CCPB-1-15CF Datasheet, PDF (2/6 Pages) Cooper Bussmann, Inc. – Compact Circuit Protector Base
Technical Data 1161
Effective April 2017
CUBEFuse Compact Circuit Protector Base (CCPB)
for Quik–Spec™ Coordination Panelboards
Specifications:
Switch ampacity and rejection breaks
• 15A, 20A, 30A, 40A, 50A, 60A, 70A, 90A and 100A
Poles
• 1-, 2- and 3-pole versions
Volts
• 600Vac (or less)
• 125Vdc (15, 20, 30, 40, 70 and 90 amp switches with ≤ 80A fuse)
Agency information
• UL 98 Listed, File E302370, Guide WHTY
• cULus to CSA Standard 22.2 No. 4, File E302370, Guide WHTY7
• CE compliant
• RoHS compliant
Terminals
Lineside bolt-on bus connector and torque
• Bolt-mounted design into Quik-Spec Coordination Panelboard bus
• #10-32-UNC Hex flange Phillips screw; 25 Lb-In (2.8 N•m)
Loadside box lug terminal and torque
• 15-60A:
• 18 to 10 AWG (1 to 6mm2) single or dual rated (same size
wire), solid or stranded – 75°C or higher - Cu only;
20 Lb-In (3.4 N•m)
• 8 to 6 AWG (10 to 16mm2) single or dual rated (same size wire),
solid or stranded – 75°C or higher - Cu only;
35 Lb-In (5.8 N•m)
• 4 AWG (25mm2) single – 75°C or higher - Cu only;
35 Lb-In (5.8 N•m)
• 100A:
• 18 to 10 AWG (1 to 6mm2) single, solid or stranded –
75°C or higher - Cu only; 25 Lb-In (2.82 N•m)
• 8 to 1 AWG (10 to 45mm2) single stranded –
75°C or higher - Cu only; 40 Lb-In (4.52 N•m)
• 6 AWG (16mm2) dual stranded (same size wire) –
75°C or higher Cu only; 45 Lb-In (5.08 N•m)
Loadside fork terminal
• Max. 30A suitable for use with #8-32UNC screw
Lockout/tagout
• 4mm shank lock
Local open fuse indication
• Light illumination requires closed circuit and minimum 90V
operating voltage
Shipping weight
• 2.03 lbs per carton
Carton quantity
• 6 poles
Environmental data
Storage and operating temperature -20°C to 75°C**
** For fuse performance under or above 25°C, consult fuse performance derating
charts.
1-Pole
CCPB-1-_CF
2-Pole
CCPB-2-_CF
Lineside bolt-on
bus connector
Loadside
box lug
terminal
Loadside
fork
terminal
3-pole
CCPB-3-_CF
Switch ON and OFF
symbols
Lockout/tagout provision
Switch handle
Local open fuse
indication light
CUBEFuse base
2