G3NA Datasheet, PDF (3/9 Pages) List of Unclassifed Manufacturers – Solid-state Relay | |||
|
◁ |
G3NA
G3NA
Characteristics
Item
Operate time
Release time
Output ON voltage drop
Leakage current
Insulation resistance
Dielectric strength
Vibration resistance
Shock resistance
Ambient temperature
Approved standards
Ambient humidity
Weight
G3NA-205B, -210B,
-220B
G3NA-240B
G3NA-410B, -420B,
-440B, -450B
G3NA-D210B
1/2 of load power source cycle + 1 ms max. (DC input)
3/2 of load power source cycle + 1 ms max. (AC input)
1 ms max. (DC input)
30 ms max. (AC input)
1/2 of load power source cycle + 1 ms max. (DC input)
3/2 of load power source cycle + 1 ms max. (AC input)
5 ms max. (DC input)
30 ms max. (AC input)
1.6 V (RMS) max.
1.8 V (RMS) max.
1.5 V max.
5 mA max. (at 100 VAC)
10 mA max. (at 200 VAC)
10 mA max. (at 200 VAC) 5 mA max. (at 200 VDC)
20 mA max. (at 400 VAC)
100 M⦠min. (at 500 VDC)
2,500 VAC, 50/60 Hz for 1 min
Malfunction: 10 to 55 Hz, 1.5-mm double amplitude
Malfunction: 1,000 m/s2
Operating: â30°C to 80°C (with no icing or condensation)
Storage: â30°C to 100°C (with no icing or condensation)
UL508 File No. E64562/CSA C22.2 (No.0, No.14) File No. LR35535 (except for G3NA-450B)
TÃV R9151660 (EN60950) (except for G3NA-4j0B)
Operating: 45% to 85%
Approx. 60 g
Approx. 70 g
Approx. 80 g
Approx. 70 g
159
|
▷ |