Conduit Opening
Tighten the connector to a torque of 1.8 to 2.2 N S m (1.37 to
1.77 N S m if it is a 1/2-14NPT). Excessive tightening torque
may damage the casing. In order to continue satisfying IP65,
apply sealing tape to the connector conduit.
The diameter of the cable must be suited to the corresponding
connector.
Wire the crimp terminal as shown in the following diagram so
that it will not come in contact with the case or cover.
Correct
Terminal screw
Incorrect
Crimp terminal
Crimp-style terminal
Recommended Connector
Size
G1/2
Pg13.5
Manufacturer
OMRON
LAPP
(see note 1)
Ohm Electric
LAPP
(see note 1)
Model
SC-6
ST-PF1/2
5360-1002
OA-W1609
ST13.5
5301-5030
Suitable cable
dia.
7.5 to 9.0 mm
6.0 to 12.0 mm
7.0 to 9.0 mm
5.0 to 12.0 mm
1/2-14NPT
LAPP
(see note 1)
ST-NPT1/2 6.0 to 12.0 mm
5301-6030
Note: 1. LAPP is a German manufacturer.
2. Ohm Denki is a Japanese manufacturer.
Maintenance and Repairs
The user must not maintain or repair equipment incorporating any
D4DS model. Contact the manufacturer of the equipment for any
maintenance or repairs required.
Crimp-style terminal
Properly attach the provided conduit cap to the unused
conduit opening and securely tighten the cap screw within a
torque range between 1.27 and 1.67 N S m when wiring the
D4DS two-conduit model.
13