E-1071 Datasheet, PDF (2/6 Pages) ETAL Group – Designed for inductive loads (DC 24 V)
Solid State Remote Power Controller E-1071-623/627
Technical data (Tambient = 25 °C, UB = DC 48 V)
General data
Ambient temperature
0…+60 °C (without condensation)
Terminals
1071-623: screw terminals
1071-627: screw-less spring-loaded
terminals
Connection: max. 2 x 2.5 mm2 solid
max. 2 x 1.5 mm2 flex with
sleeve
Housing
clamping plate: polycarbonate GV, blue
cover: polycarbonate, black
Mounting
track-mountable to EN 50022-35
Self-extinguishing properties to UL 94: V = 0; VDE 0304: grade 1
Degree of protection
housing, terminals IP20 DIN 40050
Mounting dimensions
45 x 74 x 128 mm
Mass
approx. 170 g
Technical description
Rated current IN, hold current IH
The current rating of the applicable load at its rated voltage should
be set between 0.1...3.1 A. The holding current of the load is internally
adjusted to 60 % of the set current rating. This holding current can
be measured by means of a voltmeter connected to the 2 mm current
measuring plugs (current-proportional voltage: 1 V ^= 1 A).
Setting the current rating
The current rating is set by means of a rotary switch (switch
setting 0 A - 1 A - 2 A) and a 270° potentiometer (setting range
between 0.1...1.1 A). The sum of the two settings should equal the
current rating of the load.
Example: 24 V load with IN = 1.5 A
Setting: switch 1 A + potentiometer 0.5 A
Technical description
Operating voltage UB
The max. operating voltage of the SSRPC is approx. DC 60 V. The
min. operating voltage required for 24 V solenoids depends on the
overall ohmic resistance in the load circuit. The switch-on current is
reduced by:
- the voltage drop on the load cable
- the load resistance increasing with the operating temperature of
the load.
Minimum operating voltage UB min
12345
Steuerstrom
O.K.
Fehler
Drahtbruch
GERMANY
E-1071-623
DC 24 V-Last
0,1-3,1 A
12
0
+
0,6 IN/A
0,4
0,8
0,2
0,1
1,0
1,1
ILast
= 0,6 x IN
+
1V ^=1A
IN Cable length
Cable size UB min
1A
2x50 m/2x100 m/2x200 m/2x300 m
1.5 mm2
2.5 mm2
33/35/37/40 V
32/33/35/37 V
6 7 8 9 10
2A
2x50 m/2x100 m/2x200 m/2x300 m
1.5 mm2
2.5 mm2
3A
2x50 m/2x100 m/2x200 m/2x300 m
1.5 mm2
2.5 mm2
35/38/44/49 V
34/35/39/42 V
37/41/50/58 V
35/38/42/48 V
Faulty setting of current rating
The red LED (failure indication) blinks in the event of a faulty setting.
The load is disconnected only after approx. 15 sec if the current rating
value is not corrected and the red LED will be permanently lighted.
The load capacity is no longer ensured when the minimum operating
voltage falls below UB min = 28 V. The RED LED (fault) will indicate
and the output will be switched off. Only when an operating voltage
of 29.4 V is exceeded will the load be switched on again and normal
operation status is restored.
Reset is only possible by switching on again.
The tolerance range, in which faulty setting will not be indicated, is
approx. ± 30 % of the holding current.
Ordering information
5
Resistance increase in the load circuit:
1.5 mm2 cable
approx. 2.8 Ω/100 m distance
2.5 mm2 cable
approx. 1.6 Ω/100 m distance
Type No.
E-1071
SSRPC
Maximum operating voltage UB max
The load capacity is no longer ensured when the max. operating
voltage UB max = 60 V is exceeded. The RED LED (fault) will indicate
and the output will be switched off. Only when the operating voltage
falls below 57 V will the load be switched on again and normal opera-
tion status is restored.
Terminals
623 screw terminals
627 screw-less connectors
Voltage rating of load
DC 24 V
Current rating
0.1 A...3.1 A
Switch-on current IE = pickup current
The output transistor connects the operating voltage to the inductive
load until actual switch-on of the solenoid (pickup current). After this
period the load current is set back to holding current IH.
E-1071 - 623 - DC 24 V - 0.1 A...3.1 A ordering example
Current
IN
IE
IH
ca. 10...100 ms
IN = Current rating
IE = Switch-on current/
pickup current
IH = Holding current
quick disconnection
ON
OFF time t
2
www.e-t-a.de