HPR12K-00 Datasheet, PDF (4/6 Pages) Emerson Network Power – Connecting the input power cable, output load cable and communication wire according to the below figure.
Embedded Power for
Business-Critical Continuity
5. Connector Define for I/O
5.1 Main Output Connection
Table 3 Main Output Connection Definition
No.
Designation
Identification
+48Vdc
+
MAIN OUTPUT
+48V_RTN
-
Mating Terminal screw: SUPPLY TECHNOLOGIES 6040289-0010-EC-A
MAIN OUTPUT RETURN
Rev.06.09.10
HPR12K-00
4 of 6
Terminal Type
Ring Lug, M6 screw
Ring Lug, M6 screw
5.2 PMBus Communication Connection
Use output connector below table5 , Description named CN1.
Table 4 PMBus Output Connector
Self Connector
Landwin 2051P1000T
(Astec P/N: 13866002800)
Mating Connector
Housing: Landwin 2050S1000
Pins: Landwin 2053T011P
Figure 3: Connector CN1
Signal
SCL
Table 5 Output Connection Definitions for PMBus
Name Description
Pin Qty.
Serial Clock Signal
1
Pin Number (s)
4
SDA
Serial Data Signal
1
2
Ishare
Load Share Bus
1
7
5Vsb
5Vsb External Bus
1
1
Sys_GND
Secondary Return
1
3
Unused
5
5, 6, 8, 9, 10
5.3 5V Stand-By Auxiliary Output CN2
Table 6 PMBus Output Connector
Self Connector
Tyco: 1-794528-1
(Astec P/N: 13870012770)
Mating Connector
Tyco: 794657-6
Figure 4: Connector CN2
Signal
Table 7 Output Connection Definitions foe 5V Standby
Name Description
Pin Qty.
Pin Number (s)
Stby_Rtn_Sense
Return sense for Stby ground
1
1
5Vsb
5Vsb External Bus
2
2, 3
Sys_GND
Standby GND
2
5, 6
Unused
1
4