English
Language : 

HPS3000 Datasheet, PDF (2/7 Pages) Emerson Network Power – 3000 W output power
Embedded Power for
Business-Critical Continuity
230V ac E ffic ienc y
230 Vac Efficiency
100.00
90.00
80.00
70.00
60.00
50.00
40.00
30.00
20.00
10.00
10
20
30
40
50
60
70
80
90
100
% of Total Output Pow er
Rev. 7.10.09_81
HPS3000 Series
 of 7
Output
Output rating
Set point
Total regulation range
Rated load
Minimum load
Output noise
48 V @ 62.0 A
5 Vsb @ 3.0 A
48 V @ 29.4 A
5V @ 3 A
48 V
48 V ± 10%
5 Vsb ± 4%
3000 W maximum @ 200 Vac Input
1500 W maximum @ 110 Vac Input
48 V @ 0.0 A
5 Vsb @ 0.0 A
480 mV max P-P
100 mV max P-P
Output voltage overshoot
Transient response
± 5% maximum
5% maximum deviation
Max units in parallel
Up to 4
Short circuit protection
120% - 130% of rated output
Output isolation
Per POE specs
Forced load sharing
Within 10% of all shared outputs
Over current protection (OCP) 120% to 130%
100% to 125%
Over voltage protection (OVP) 110% to 120%
110% to 125%
Over temperature protection 10 - 15 deg C above safe
operating area
180 - 264 Vac
90 - 140 Vac
Programmable ±10% through I2C serial bus
Line/load/transient when measured at output connection
No derating over operating temp range
No loss of regulation
48 V output
5 Vsb output
Measured with a 0.1µF Ceramic and 10 µF Tantalum capacitor on any
input
Nominal Voltage Setting
50% load step @ 1 A/us
Step load valid between 10% to 100% of output rating.
Total power in 1U 19” rack is 12 KW
Output to return
>2000 Vac
Digital sharing control
48 V output
5 Vsb output
48 V output
5 Vsb output
Both PFC and output converter monitored
5 Vsb will operate under overtemperature condition.
Built in hysteresis
Environmental Specifications
Vibration/Shock:
Non-operational 5G Sine sweep from 5 Hz to 500 Hz, dwelling at resonant frequencies for 1 hour each
Operating temperature:­­
Storage Temperature:
Cooling
-10 ° to +40 °C
-40 ° to +85 °C
External fans with Fan Fail and Fan Speed control
Operating Relative Humidity: 5% to 95% non-condensing
Storage Relative Humidity: 5% to 95% non-condensing
Operating Altitude
Up to 10,000 feet above sea level
Storage Altitude:
Up to 30,000 feet above sea level
RoHS Compliant:
Yes