HPS3000 Datasheet, PDF (1/7 Pages) Emerson Network Power – 3000 W output power | |||
|
Embedded Power for
Business-Critical Continuity
HPS3000 Series
3000 Watts
Distributed Power Bulk Front-End
Single Output
Rev. 7.10.09_81
HPS3000 Series
of 7
Special Features
⢠3000 W output power
⢠40 W/cu-in
⢠Optional customer provided air
⢠1U x 3U form factor
⢠N+1 Redundant
⢠Hot-swap
⢠Internal OR-ing
⢠5 V housekeeping
⢠High efficiency 89% @ 200 Vac,
100% load
⢠Variable speed âsmart fansâ
⢠One year warranty
Compliance
⢠POE Isolation
⢠EMI Class B - EN55022, Level âAâ
⢠EN61000 Immunity
Electrical Specifications
Input
Input raÂnge (operating):
Input range (nominal):
Frequency:
180 - 264 Vac
90 - 140 Vac
200 Vac
110 Vac
43 to 63 Hz
Input through Card Edge Connection
on same end as DC output
Input fusing:
Inrush current:
Internal 25 A fuses
â¤40 A peak
Both lines fused
Either hot or cold start
Power factor:
0.97 typical
Meets EN61000-3-2
Harmonics:
Meets IEC 1000-3-2
requirements
@ 50% load
Input current:
19 A max input current
Holdup time:
10 ms minimum
At full rated load
Leakage current:
1.4 mA
At 240 Vac
Power line transient:
MOV directly after the fuse
Safety
⢠UL/cUL
⢠CSA
⢠China
⢠Nemko
⢠CB Report
⢠CSA 22.2
60950
60950
CCC
TUV
60950
|
▷ |