English
Language : 

HPS3000 Datasheet, PDF (1/7 Pages) Emerson Network Power – 3000 W output power
Embedded Power for
Business-Critical Continuity
HPS3000 Series
3000 Watts
Distributed Power Bulk Front-End
Single Output
Rev. 7.10.09_81
HPS3000 Series
 of 7
Special Features
• 3000 W output power
• 40 W/cu-in
• Optional customer provided air
• 1U x 3U form factor
• N+1 Redundant
• Hot-swap
• Internal OR-ing
• 5 V housekeeping
• High efficiency 89% @ 200 Vac,
100% load
• Variable speed “smart fans”
• One year warranty
Compliance
• POE Isolation
• EMI Class B - EN55022, Level “A”
• EN61000 Immunity
Electrical Specifications
Input
Input ra­nge (operating):
Input range (nominal):
Frequency:
180 - 264 Vac
90 - 140 Vac
200 Vac
110 Vac
43 to 63 Hz
Input through Card Edge Connection
on same end as DC output
Input fusing:
Inrush current:
Internal 25 A fuses
≤40 A peak
Both lines fused
Either hot or cold start
Power factor:
0.97 typical
Meets EN61000-3-2
Harmonics:
Meets IEC 1000-3-2
requirements
@ 50% load
Input current:
19 A max input current
Holdup time:
10 ms minimum
At full rated load
Leakage current:
1.4 mA
At 240 Vac
Power line transient:
MOV directly after the fuse
Safety
• UL/cUL
• CSA
• China
• Nemko
• CB Report
• CSA 22.2
60950
60950
CCC
TUV
60950