TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
24V 120W 2 Phase / DRP-24V120W2BN
Safety Instructions
 Vertical Mounting
 Horizontal Mounting
• ALWAYS switch mains of input power OFF before connecting and disconnecting the input voltage to the unit. If mains are not
turned OFF, there is risk of explosion / severe damage.
• To guarantee sufficient convection cooling, please refer to the following instructions to ensure sufficient clearance
around the device.
Vertical Mounting: 50mm (1.97 inch) above and below the device as well as a lateral distance of 5mm (0.20 inch) to other
units.
Horizontal Mounting: 50mm (1.97 inch) above and below the device as well as a lateral distance of 50mm (1.97 inch) to
other units.
• Note that the enclosure of the device can become very hot depending on the surrounding air temperature and load of the power
supply. Risk of burns!
• The main power must be turned off before connecting or disconnecting wires to the terminals.
• DO NOT insert any objects into the unit.
• Hazardous voltages may be present for up to 5 minutes after the input mains voltage is disconnected. Do not touch the unit during
this time.
• The power supplies unit should be installed in minimum IP54 rated enclosure.
• The power supplies are built in units and must be installed in a cabinet or room (condensation free environment and indoor
location) that is relatively free of conductive contaminants.
• CAUTION: Double pole/neutral fusing.
• CAUTION: “For use in a controlled environment”.
9
All parameters are specified at 25°C ambient and AC x 2 input unless otherwise indicated.