English
Language : 

DRP-24V120W2BN Datasheet, PDF (2/14 Pages) Delta Electronics, Inc. – CliQ II DIN Rail Power Supply
TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
24V 120W 2 Phase / DRP-24V120W2BN
Specifications
Input Ratings / Characteristics
Nominal Input Voltage
Input Voltage Range
Nominal Input Frequency
Input Frequency Range
DC Input Voltage Range*
Input Current
Efficiency at 100% Load
Max Power Dissipation
Max Inrush Current (Cold Start)
Leakage Current
*Safety approval according to IEC/EN/UL 60950-1.
0% load
100% load
2 x 200-500Vac (2-Phase)
200-277Vac (Single Phase)
2 x 180-550Vac (2-Phase)
180-305Vac (Single Phase)
50-60Hz
47-63Hz
254-780Vdc
< 1.20A @ 2 x 230Vac, < 0.65A @ 2 x 400Vac
> 90.0% @ 2 x 400Vac
< 1.6W @ 2 x 200Vac, < 2.5W @ 2 x 500Vac
< 17W @ 2 x 200Vac, < 15W @ 2 x 500Vac
< 50A @ 2 x 200Vac
< 3.5mA @ 500Vac
Output Ratings / Characteristics**
Nominal Output Voltage
Factory Set Point Tolerance
Output Voltage Adjustment Range
Output Current
24Vdc
24Vdc ± 2%
24-28Vdc
5.00A (continuously operating at 24V)
6.00A (Power Boost for 3 seconds at 24V, refer to the details in
the Functions section)
Output Power
120W (continuously operating at 24V)
144W (Power Boost for 3 seconds at 24V, refer to the details in
the Functions section)
Line Regulation
Load Regulation
PARD*** (20MHz)
Rise Time
Start-up Time
Hold-up Time
Dynamic Response
(Overshoot & Undershoot O/P Voltage)
< 0.5% typ. (@ 200-550Vac input, 100% load)
< 1% typ. (@ 200-550Vac input, 0-100% load)
< 150mVpp
< 70ms @ nominal input (100% load)
< 2,500ms @ nominal input (100% load)
>10ms @ 2 x 230Vac (100% load)
> 50ms @ 2 x 400Vac (100% load)
± 5% @ 0-100% load
Start-up with Capacitive Loads
Functional
DC OK Relay Contact
5,000µF Max
30V / 1A
The relay is usually closed when the output is normal
**For power de-rating from 60°C to 70°C, see power de-rating on page 3.
***PARD is measured with an AC coupling mode, 5cm wires, and in parallel with 0.1μF ceramic capacitor & 47μF electrolytic capacitor.
2
All parameters are specified at 25°C ambient and AC x 2 input unless otherwise indicated.
www.DeltaPSU.com (December 2016, Rev. 02)