DRP-24V120W2BN Datasheet, PDF (11/14 Pages) Delta Electronics, Inc. – CliQ II DIN Rail Power Supply
TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
24V 120W 2 Phase / DRP-24V120W2BN
Power Boost
Power Boost is the reserve power available
constantly that allows reliable startup to support
sudden and short spike of loads with high inrush
current typically during turn on to remove the
need of more expensive higher rated power
supply unit. After the output has reached its
steady state set value, the power supply can
support surge loads with a higher short-term
power demand up to 120% of maximum rated
load (IO Max), for a maximum duration of 3
seconds. The Power Boost is also available to
repeatedly basis with according to the condition of
an average (R.M.S) output power shall not
exceed continuous operating condition or refer to
duty cycle calculation below.
𝐷𝑢𝑡𝑦 𝑐𝑦𝑐𝑙𝑒 (%) =
𝑇𝑃
𝑇𝑜𝑡𝑎𝑙 𝑇𝑖𝑚𝑒
𝐴𝑣𝑒𝑟𝑎𝑔𝑒 𝑂𝑢𝑡𝑝𝑢𝑡 𝑃𝑜𝑤𝑒𝑟 (𝑃𝐴𝑣𝑔)
(𝑃𝑜𝑤𝑒𝑟 𝐵𝑜𝑜𝑠𝑡
=
× 𝑇𝑃) + (𝑁𝑜𝑛-𝑃𝑒𝑎𝑘 𝑃𝑜𝑤𝑒𝑟 × 𝑇𝑁)
𝑇𝑜𝑡𝑎𝑙 𝑇𝑖𝑚𝑒
OR
𝑁𝑜𝑛-𝑃𝑒𝑎𝑘 𝑃𝑜𝑤𝑒𝑟 =
�𝑃𝐴𝑣𝑔
× 𝑇𝑜𝑡𝑎𝑙 𝑇𝑖𝑚𝑒� − (𝑃𝑜𝑤𝑒𝑟 𝐵𝑜𝑜𝑠𝑡
𝑇𝑁
× 𝑇𝑃)
 An example of Power Boost and Average Output Power
Power Boost
120%
120%
Peak Power
(WP)
144
144
Power Boost
Duration (TP)
3 sec
3 sec
Duty Cycle
10%
15%
Non-Peak
Power (WN)
114W
117W
Non-Peak Power
Duration (TN)
27 sec
17 sec
Total Time
(T)
30 sec
20 sec
It is not recommended to prolong the duration of Power Boost to be longer than the specified duty cycle calculation, this may cause
damage to the PSU.
External Input Protection Device
The unit is protected at the L pin, with an internal fuse that cannot be replaced. The power supply has been tested and approved on
20A (UL) and 16A (IEC) branch circuits without additional protection device. An external protection device is only required if the
supplying branch has an ampacity greater than above. Thus, if an external protective device is necessary, or, utilized, please refer a
minimum value in instruction sheet with B or C characteristic breaker.
11
All parameters are specified at 25°C ambient and AC x 2 input unless otherwise indicated.