DRC-24V100W1AX Datasheet, PDF (8/11 Pages) Delta Electronics, Inc. – Protection Class II, Double Isolation
TECHNICAL DATASHEET
Chrome DIN Rail Power Supply
24V 91.2W 1 Phase (Class II & NEC Class 2) / DRC-24V100W1A□
Safety Instructions
– ALWAYS switch mains of input power OFF before
connecting and disconnecting the input voltage to the unit.
If mains are not turned OFF, there is risk of explosion /
severe damage.
– To guarantee sufficient convection cooling, keep a
distance of 50mm (1.97 inch) above and below the
device as well as a lateral distance of 25mm (0.98 inch)
to other units.
– Note that the enclosure of the device can become very hot
depending on the surrounding air temperature and load of
the power supply. Risk of burns!
– DO NOT insert any objects into the unit.
– Hazardous voltages may be present for up to 5 minutes
after the input mains voltage is disconnected. Do not touch
the unit during this time.
– The power supplies unit should be installed in minimum
IP54 rated enclosure.
– The power supplies are built in units and must be installed
in a cabinet or room (condensation free environment and
indoor location) that is relatively free of conductive
contaminants.
Functions
■ Graph illustrating the Start-up Time, Rise Time, and Hold-up Time
Start-up Time
The time required for the output voltage to reach 90% of its final steady state set value, after the input voltage is applied.
Rise Time
The time required for the output voltage to change from 10% to 90% of its final steady state set value.
Hold-up Time
Time between the collapse of the AC input voltage, and the output falling to 95% of its steady state set value.
8
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
www.DeltaPSU.com (April 2016, Rev. 02)