TECHNICAL DATASHEET
Chrome DIN Rail Power Supply
24V 91.2W 1 Phase (Class II & NEC Class 2) / DRC-24V100W1A□
Environment
Surrounding Air Temperature
Power De-rating
Operating Humidity
Operating Altitude
Shock Test
Vibration
Pollution Degree
Protections
Overvoltage
Overload / Overcurrent
Over Temperature
Short Circuit
Internal Fuse
Degree of Protection
Protection Against Shock
*PE: Primary Earth
Reliability Data
MTBF
Expected Cap Life Time
Operating -25°C to +71°C
Storage -25°C to +85°C
> 55°C de-rate power by 2.5% / °C
5 to 95% RH (Non-Condensing)
0 to 2,000 Meters (6,560 ft.)
Operating IEC 60068-2-27, Half Sine Wave: 4G for a duration of 22ms,
3 shocks for each 3 directions, 9 times in total
Operating IEC 60068-2-6, Sine Wave: 10-500Hz @ 19.6m/S² (2G peak);
10 min per cycle, 60 min for all X, Y, Z directions
2
< 34.8V, SELV Output, Latch Mode
> 102~108% of rated load current,
Fold Forward Mode (current rises, voltage drops)
Auto-recovery when the fault is removed
> 75°C Surrounding Air Temperature @ 100% load, Latch
Mode
Hicc-up Mode, Non-Latching
(Auto-Recovery when the fault is removed)
T3.15AH
IP20
Class II (No PE* connection is required)
Telcordia SR-332 > 500,000 hrs., I/P: 100Vac
O/P: 100% load, Ta: 35°C
10 years (115Vac & 230Vac, 50% load @ 40°C)
3
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.