English
Language : 

DRP024V060W1AZ_12 Datasheet, PDF (4/11 Pages) Delta Electronics, Inc. – CliQ DIN Rail Power Supply
TECHNICAL DATASHEET
CliQ DIN Rail Power Supply
24V 60W 1 Phase / DRP024V060W1AZ
Safety Standards / Directives
Electronic Equipment in Power Installations
Electrical Safety
Industrial Control Equipment
Hazardous Location / ATEX
II 3G ATEX 94/9/EC;
IECEX Test Report
CE
Material and Parts
Galvanic Isolation
EMC
EMC / Emissions
Immunity to
Electrostatic Discharge
Radiated Field
Electrical Fast Transient / Burst
Surge
Conducted
Power Frequency Magnetic Fields
Voltage Dips
Low Energy Pulse Test (Ring Wave)
1) Criteria A: Normal performance within the specification limits
2) Asymmetrical: Common mode (Line to earth)
3) Symmetrical: Differential mode (Line to line)
EN50718 / IEC62103
SIQ to EN60950-1, UL/cUL recognized to UL60950-1,
CSA C22.2 No. 60950-1, CB scheme to IEC60950-1,
CSA to UL60950-1 and CSA C22.2 No. 60950-1
(File No. 181564)
UL/cUL listed to UL508 and CSA C22.2 No. 107.1-01,
CSA to CSA C22.2 No. 107.1-01 (File No. 181564)
Pending
Certificate No. Pending
For IEC60079-0, IEC60079-15
In conformance with EMC Directive 2004/108/EC and
Low Voltage Directive 2006/95/EC
RoHS Directive 2011/65/EU Compliant
Input to Output 4.0KVac
Input to Ground 1.5KVac
Output to Ground 1.5KVac
CISPR22, EN55022, EN55011, FCC Title 47: Class B
EN61000-4-2
EN61000-4-3
EN61000-4-4
IEC6100-4-5
EN61000-4-6
EN61000-4-8
EN61000-4-11
IEC61000-4-12
Level 4 Criteria A1)
Air Discharge: 15kV
Contact Discharge: 8kV
Level 3 Criteria A1)
80MHz–1GHz, 10V/M with 1kHz tone / 80% modulation
Level 3 Criteria A1)
2kV
Level 3 Criteria A1)
Common Mode2): 2kV
Differential Mode3): 1kV
Level 3 Criteria A1)
150kHz-80MHz, 10Vrms
Level 3 Criteria A1)
10A/Meter
Level 3 Criteria A1)
100% dip; 1 cycle (20ms); Self Recoverable
Level 3 Criteria A1)
Common Mode2): 2kV
Differential Mode3): 1kV
4
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (December 2012, Rev. 02)