DRP024V060W1AZ_12 Datasheet, PDF (3/11 Pages) Delta Electronics, Inc. – CliQ DIN Rail Power Supply
TECHNICAL DATASHEET
CliQ DIN Rail Power Supply
24V 60W 1 Phase / DRP024V060W1AZ
Environment
Surrounding Air Temperature
Power De-rating
Operating Humidity
Operating Altitude
Shock Test (Non-Operating)
Vibration (Non-Operating)
Bump
Pollution Degree
Protections
Overvoltage
Overload / Overcurrent
Over Temperature
Short Circuit
Degree of Protection
Protection Against Shock
*PE: Primary Earth
Reliability Data
MTBF
Expected Cap Life Time
Operating
Storage
-20°C to +75°C
-25°C to +85°C
< 0°C to -20°C de-rate power by 1% / °C
> 50°C de-rate power by 2.5% / °C
> 70°C de-rate power by 4% / °C
< 95% RH (Non-Condensing)
3,000 Meters
IEC60068-2-27, 30G (300m/S²) for a duration of 18ms
IEC60068-2-6, 10Hz to 150Hz @ 50m/S² (5G peak);
90 min per axis for all X, Y, Z direction
IEC60068-2-29; 11ms / 10gn
2
32V +10%, SELV Output, Hicc-up Mode,
Non-Latching (Auto-Recovery)
> 150% of rated load current, Hicc-up Mode,
Non-Latching (Auto-Recovery)
< 80°C Surrounding Air Temperature @ 100% load,
Non-Latching (Auto-Recovery)
Hicc-up Mode, Non-Latching
(Auto-Recovery when the fault is removed)
IPX0
Class I without PE* connection
> 800,000 hrs. as per Telcordia SR-332
10 years (115Vac & 230Vac, 50% load @ 40°C)
3
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (December 2012, Rev. 02)