English
Language : 

SMCW6150 Datasheet, PDF (10/16 Pages) celduc-relais – Solid State Relays For Motor Control
S/MOT/SMCW6150/A/22/07/99
1W240020
Page 10/16
Solid State Relays
For Motor Control
celduc®
relais
STANDARDS
IMMUNITY LEVEL WITHIN ELECTROMAGNETIC COMPATIBILITY (E.M.C.)
CHARACTERISTICS
LABELS
VALUES
(Given at 20°C ambient unless otherwise specified)
Electrostatic discharges
EN
61000-4-2
8kV in the air
4kV contact
Radiated Electromagnetic Fields
EN
61000-4-3
10V/m
Fast Transient Bursts
EN
61000-4-4
2kV direct coupling on the power side
2kV clamped coupling on the input side
Electric chocks
EN
1kV direct coupling differential mode (Input and output sides)
61000-4-5 2kV direct coupling common mode (Input and output sides)
Voltage Drop
EN
61000-4-11
EMISSION LEVEL WITHIN ELECTROMAGNETIC COMPATIBILITY (E.M.C.)
CHARACTERISTICS
LABELS
VALUES
(Given at 20°C ambient unless otherwise specified)
In compliance with the standards
Conducted Disturbances
EN55011
for industrial field
In compliance with the standards
for domestic field with an external bypass contactor
Radiated Disturbances
EN55011
<30dbµV for the frequency range 30->230MHz
<37dbµV for the frequency range 230->1000MHz
The conducted or radiated disturbances generated by solid
state relays depend on the wiring and load configuration.
The test method recommended by the European standards
and concerning electromagnetic compatibility leading to results
far from reality, we decided to advise our customer in order to
adapt their filtering scheme to their application.
The European standard EN60947-4-2 requires the
Remarks Concerning Filtering
measurement to be done at full on state (end of the softstarting
period). Therefore, our products are below the industrial field
required levels on inductive load like the induction motor and
no additional filter is needed.
The starting period that may last several minutes
generates enough interference to disturb sensitive devices
located near the softstarter. If any, please contact us so that we
can help you to choose the right filter.
CHARACTERISTICS
Standard
Protection Level
Protection For Direct Touch
LOW VOLTAGE DIRECTIVE
LABELS
VALUES
(Given at 20°C ambient unless otherwise specified)
EN60947-4-2
IP
2L0
According to V.D.E. 160 part 100 : Back hand and finger safety
REMARKS
No state
changing or
destruction
No state
changing or
destruction
No state
changing or
destruction
No state
changing or
destruction
REMARKS
REMARKS
CHARACTERISTICS
CE Marking
c UL US
VDE 0805
LABELS
EN
60947-4-2
UL508
EN60950
APPROVALS
VALUES
(Given at 20°C ambient unless otherwise specified)
Yes
Pending
Pending
REMARKS
Office
environment