English
Language : 

SMCW6150 Datasheet, PDF (1/16 Pages) celduc-relais – Solid State Relays For Motor Control
celduc®
relais
Solid State Relays
For Motor Control
S/MOT/SMCW6150/A/22/07/99
1W240020
Page 1/16
INDUCTION MOTOR SOLID-STATE REDUCED
VOLTAGE STARTER (SOFTSTARTER) WITH
SOFTSTOP FEATURE (PRELIMINARY DATA)
SMCW6150
celduc relais SMCV can be employed everywhere using a costly and relatively big
variable speed controller is not required (pumps, fans, compressors, conveyors, …).
Its six thyristor structure working like a full wave phase angle controller (both positive
and negative cycles are controlled), allows to reduce efficiently the induction motor starting current
as well as the motor starting torque. This motor starting current reduction allows to optimize
the mains grid as well as its protections and avoid having voltage fluctuations leading to
ambient light variations also called "flicker".
Built to help the user to get his assembly in compliance with the European directives and
standards, this product easy fits in the existing application without any modification of the wiring
field configuration. Thus, the SMCV can easily replace an electromechanical star-delta starter
without changing the motor coupling! In a project including a three phase induction motor it can be
implemented like a usual three phase electromechanical contactor. Furthermore, its ability to be
installed inside the delta wiring allows this device to drive 1.73 times more current than a
standard on line softstarter,
The SMCV also have diagnostic and self-test functions to inform people involved in the
machine maintenance and to reduce the cost and the delay to restart the production.
Induction Motor
Softstarter
200 - 480VAC
->15kW (Y)
->26kW (D)
Max. Motor Power @40°C
Star (Y)
Delta (D)
400VAC 230VAC 400VAC 230VAC
15kW 8.6kW 26kW 15kW
MAIN CHARACTERISTICS
IAC53a @40°C
Max. EN60947-4-2
Phase
to
Phase
Voltage
Mains
Frequency
30A
22.5A
200 to
480VAC
40 to 65Hz
Input
10 to
24VDC
Status
Outputs
24V / 1A
AC/DC
In/Out/Case
Isolation
4kV
Operating
Tempera-
ture
-40 to
+100°C
BENEFIT FOR MOTOR STARTING
DIRECT ON LINE (DOL) STARTING
TYPICAL WIRINGS
STAR (Y)
DELTA (D)
Î Mechanical part stress:
- noise
Î - Maintenance costs
High inrush current:
- Motor and mains
protections oversized
- Risk of flicker
SOFTSTARTING WITH SMCV
Î Softstarting:
- Noise reduction
- Maintenance cost
Î reduction
No more high inrush
current:
- Motor and mains
protections optimization
- No more harmonic or
flicker problems
Proud to serve you
Characteristics may change without notice
celduc ®
relais