GA1-B0-24-620-11-DC Datasheet, PDF (3/4 Pages) Carling Technologies – Circuit Breaker
G–Series DIN Rail – Ordering Scheme & Time Delay Table | 3
G
1
Series
A
2
Actuator
1
3
Poles
—B
4
Circuit
1 SERIES
G
0 — 24 — 620 — 1
5
Aux/Alarm
Switch
6
Frequency
& Delay
7
Current Rating
8
Terminal
8 TERMINAL
1 Screw Terminal
1 —D
9
Actuator
Color &
Legend
10
Rating
C
11
Agency
Approval
2 ACTUATOR1
A Handle, one per pole
3 POLE
1 One
2 Two
4 CIRCUIT
A2 Switch Only (no coil)
S Mid-Trip Handle, one per pole
3 Three
4 Four1
B Series Trip (current)
9 ACTUATOR COLOR & LEGEND
Actuator Color
I-O
ON-OFF
White
A
B
Black
C
D
Red
F
G
Green
H
J
Blue
K
L
Yellow
M
N
Gray
P
Q
Orange
R
S
Dual
1
2
3
4
5
6
7
8
Legend Color
Black
White
White
White
White
Black
Black
Black
5 AUXILIARY/ALARM SWITCH3
0
w/o Aux Switch
1 S.P.D.T., screw terminal
3 S.P.D.T. screw terminal/
Gold contacts
6 FREQUENCY & DELAY
032 DC 50/60Hz, Switch Only
10 DC Instantaneous
11 DC Ultra Short
12 DC Short
14 DC Medium
16 DC Long
20 50/60Hz Instantaneous
21 50/60Hz Ultra Short
22 50/60Hz Short
7 CURRENT RATING (AMPERES)
CODE AMPERES
220 0.200
225 0.250
230 0.300
235 0.350
240 0.400
245 0.450
250 0.500
255 0.550
260 0.600
265 0.650
270 0.700
275 0.750
280 0.800
285 0.850
290 0.900
295 0.950
410 1.00
512 1.25
415 1.50
517 1.75
420 2.00
522 2.25
425 2.50
527 2.75
430 3.00
435 3.50
440 4.00
445 4.50
450 5.00
455 5.50
24 50/60Hz Medium
26 50/60Hz Long
424 50/60Hz Short, Hi-Inrush
444 50/60Hz Medium, Hi-Inrush
464 50/60Hz Long, Hi-Inrush
524 DC Short, Hi-Inrush
544 DC Medium, Hi-Inrush
564 DC Long, Hi-Inrush
460 6.00
465 6.50
470 7.00
475 7.50
480 8.00
485 8.50
490 9.00
495 9.50
610 10.00
710 10.50
611 11.00
711 11.50
612 12.00
712 12.50
613 13.00
614 14.00
615 15.00
616 16.00
617 17.00
618 18.00
620 20.00
622 22.00
624 24.00
625 25.00
630 30.00
635 35.00
640 40.00
650 50.00
660 60.00
663 63.00
10 MAX. APPLICATION RATING
M 80VDC
D 240VAC
H 480VAC 5
11 AGENCY APPROVAL
A Without approvals
C UL Recognized, CUL
E UL Recognized, CUL, TUV
Notes:
1 4th pole for neutral break only.
2 Switch only construction currently only available on multipole units when at least one
pole is a protected pole.
3 On multipole breakers, one auxilary switch is supplied, mounted in the extreme right
pole. (when viewed from back.)
4 High Inrush delays limited to 50A max.
5 480V only available as three or four pole. Two pole is not available.
Time Delay Values
PERCENT OF RATED CURRENT
Notes:
Delay Curves 11,12,14,16,21,22,24,26,42,44,46,52,54,56: Breakers to hold 100% and must trip at 125% of rated current and greater within the time limit shown in this curve.
Delay Curves 10,20: Breakers to hold 100% and must trip at 150% of rated current and greater within the time limit shown in this curve.
All Curves: Curve data shown represents breaker response at ambient temperature of 77°F (25°C) with no preloading. Breakers are mounted in standard wall-mount position.
On 50 amp and less current ratings, the minimum inrush pulse tolerance handling capability is 12 times the rated current on standard delays and 25 times the rated current on high inrush delays.
These values are based on a 60 Hz 1/2 cycle, 8.33 ms pulse. High inrush delays should be specified for applications with high initial surge currents of short duration such as switching power supplies,
highly capacitive loads and transformer loads.