Language : 

GA1-B0-24-620-11-DC Datasheet, PDF (2/4 Pages) Carling Technologies – Circuit Breaker
2 | G–Series DIN Rail – General Specifications
Electrical Tables
Table A: Lists UL Recognized, CSA Accepted and TUV Certified configurations and performance capabilities as a Component
Supplementary Protector.
CIRCUIT
CONFIGURATION
SERIES
MAX
RATING
80
240
240
480
G SERIES - COMPONENT SUPPLEMENTARY PROTECTOR
VOLTAGE
CURRENT
SHORT CIRCUIT CAPACITY (AMPS)
FREQ.
DC
50/60
50/60
50/60
PHASE
--
1
1
3
FULL LOAD
63
63
63
63
MINIMUM
POLES
1
1
2
3
UL
WITHOUT BACKUP
FUSE
3000
3000
3000
1500
CSA
WITHOUT BACKUP
FUSE
3000
3000
3000
1500
TUV
WITHOUT BACKUP
FUSE
1500
1500
1500
415V, 1000
APPLICATION CODES
UL
TC1, OL1, U1
TC1, OL1, U1
TC1, OL1, U1
TC1, OL1, U1
CSA
TC1, OL1, U1
TC1, OL1, U1
TC1, OL1, U1
TC1, OL1, U1
Electrical
Maximum Voltage
Current Rating
Auxiliary Switch Rating
Insulation Resistance
Dielectric Strength
Resistance, Impedance
AC: 240VAC (single pole), 440VAC
(3 poles, additional pole shall be
dedicated for neutral break)
DC: 80VDC (single pole and multipole)
0.2 – 63A. Other ratings available, see
Ordering Scheme.
(optional) Integrated, load side.
SPST, 3A – 125Vac, 2A – 30Vdc.
Auxiliary switch senses the on & off
position of circuit breaker handle, as
well as contact arm position. Switch
connections are screw terminals.
Minimum of 100 Megohms at 500 VDC.
UL, CSA: 1960 V 50/60 Hz for one
minute between all electrically isolated
terminals. G-Series Circuit Breakers
comply with the 8mm spacing and
3750V 50/60 Hz dielectric requirements
from hazardous voltage to operator
accessible surfaces, between
adjacent poles and from main circuits
to auxiliary circuits per Publications EN
60950 and VDE 0805.
Values from Line to Load Terminal -
based on Series Trip Circuit Breaker.
1000
RESISTANCE, IMPEDANCE VALUES
from Line to Load Terminals
(Values Based on Series Trip Circuit Breaker)
100
10
6
O
H1
M
S
0.1
0.01
0.001
0.01
0.1
1
10
100
AMPERE RATING
Mechanical
Endurance
Trip Free
Trip Indication
Fire and smoke
Physical
Number of Poles
Weight
Standard Colors
10,000 ON-OFF operations @ 6 per
minute; with rated current & voltage.
All G-Series circuit breakers will trip
on overload, even when actuator is
forcibly held in the ON position.
The operating actuator moves
positively to the OFF position when an
overload causes the breaker to trip.
With mid-trip, the handle moves to the
mid position on electrical trip of the
circuit breaker. With mid trip handle
with alarm switch, handle moves to
the mid position and the alarm switch
actuates when the circuit breaker is
electrically tripped.
NF F16-101/102, DIN5510 & BS6853
fire and smoke material selection &
application for electrical equipment.
1 pole ≤ 63A, 2 poles ≤ 63A per pole
Approx.172 grams/pole ( 4.13 oz).
Housing: Black
Environmental
Designed in accordance with requirements of specification
MIL-PRF-55629 & MIL-STD-202 as follows:
Shock
Withstands 100 Gs, 6ms sawtooth
while carrying rated current per
Method 213, Test Condition “I”.
Instantaneous and ultrashort curves
tested @ 90% of rated current.
Vibration
Withstands 0.060” excursion from
10-55 Hz & 10 Gs 55-500 Hz, @ rated
current per Method 204C, Test Cond.
A. Instantaneous & ultrashort curves
tested @ 90% of rated current.
Moisture Resistance Method 106D, i.e., ten 24-hour cycles
@ +25°C to +65°C, 80-98% RH.
Salt Spray
Method 101, Condition A (90-95% RH
@ 5% NaCl Solution, 96 hrs).
Thermal Shock
Method 107D, Condition A (five cycles
@ -55°C to +25°C to +85°C to +25°C).
Operating Temperature -40°C to +85°C
*Manufacturer reserves the right to change product specification without prior notice.