DS1100SDC Datasheet, PDF (3/8 Pages) Artesyn Technologies – Distributed Power System
DS1100SDC Data Sheet
Electrical Specifications
Timing Specifications
Tsb_On
Tsb_INPUT_OK
Tsb_Vout
TINPUT_On_Delay
TPWR_GOOD_On
TINPUT_OK_Delay
TPWR_GOOD_Hold-up
TVout_Hold-up
Tsb_Hold-up
TPWR_GOOD_Off
TPSON_On_Delay
TPWOK_Low
Description
Delay from DC input being applied to standby output being within regulation
Delay from standby output to INPUT_OK assertion
Delay from standby output to main output voltage being within regulation
Delay from DC input being applied to main output being within regulation
Delay from output voltages within regulation limits to PWOK asserted
Delay from loss of DC input to assertion of INPUT_OK
Delay from loss of DC input to deassertion of PWOK
Delay from loss of DC input to main output being within regulation
Delay from loss of DC input to standby output being within regulation
Delay from deassertion of PWOK to output falling out of regulation
Delay from PSON assertion to output being within regulation
Duration of PWOK being in deasserted state during an ON/OFF cycle of PSU
Min
20
See note below
100
1
150
1
N/A
Max
1700
20
300
2200
1000
6
0.2
350
N/A
Unit
ms
ms
ms
ms
ms
ms
ms
ms
ms
ms
ms
Note: T : sb_hold-up tested at 1A load on standby output
T : sb_INPUT_OK INPUT_OK can assert earlier than the standby output
Environmental Specifications
Operating temperature
DS1100SDC-3: 1100W from 0 to 50 °C
DS1100SDC-3-001: 1100W from 0 to 40°C
Operating altitude
up to 10,000 feet with derating
Operating relative humidity
20% to 80% non-condensing
Non-operating temperature
-40 to +70 °C
Non-operating relative humidity
10% to 95% non-condensing
Non-operating altitude
up to 50,000 feet
Vibration and shock
Standard operating/non-operating shock/vibration
ROHS compliance
YES
MTBF
200,000 hours per Telcordia Issue 2, Method 1, Case 3 at 25 °C ambient at full load
Operating life
Minimum of 5 years
Reliability
All electronic component derating analysis is done at maximum ambient, 80% of maximum rated load,
nominal input line voltage.