English
Language : 

DS1100SDC Datasheet, PDF (2/8 Pages) Artesyn Technologies – Distributed Power System
DS1100SDC Data Sheet
Electrical Specifications
Protections
Main Output
Overcurrent protection2
Overvoltage protection1
MIN
120%
13.5 V
NOM
Undervoltage protection
10.5 V
Overtemperature protection
Yes
Fan fault protection
Yes
Standby Output
Overcurrent protection3
Overvoltage protection3
120%
13.5 V
Undervoltage protection
LED Indicators
10.0 V
A single bi-color LED is used to indicate the power supply status.
Status LED
No DC input to PSU
Off
Main output ON
Solid GREEN
Standby mode or Power supply failure (OCP, OVP, OTP, FAN FAULT:)
Firmware Reporting And Monitoring
Blinking AMBER
Accuracy Range
Output loading
5 to 20%
20 to 50%
Input voltage
2%
Input current
±0.55 A fixed error
±4%
Input power
±1.25 W at < 125 W input
±1.25%
Output voltage
±2%
Output current
0.3 A fixed error
±2%
Temperature
EIN
Fan speed
±15% from 10% to 20% load
±5 °C on the operating range
±5%
Actual RPM ±250 RPM
PMBus
YES
Remote ON/OFF
YES
1 Latch mode
2 Autorecovery if the overcurrent is less than 120% and last only for <500 ms
3 Standby protection is auto-recovery
MAX
150%
15.0 V
11.0 V
150%
15.0 V
11.0 V
50 to 100%