English
Language : 

700-SH Datasheet, PDF (4/7 Pages) Allen-Bradley – Solid-State Relays
Bulletin 700-SH
Solid-State Relays
Specifications, Continued
Cat. No.
Load Switching Method/
Device
Pick-up Time
Drop-out Time
Output ON Voltage Drop
Output Leakage Current
Output VDRM, VCEO (V)
Output di/dt (A/uS)
Output dv/dt (V/uS)
Output I2t (A2S)
Output Tj °C Max.
Insulation Resistance
Dielectric Strength
Vibration Resistance (max.)
Shock Resistance (max.)
Ambient Temperature
Ambient Humidity
Standards ➊
Weight
700-SH05G, -SH10G, SH25G
Characteristics
700-SH40G
700-SH10H, -SH25H, SH40H
Triac
Thyristor
1/2 of load power source + 1 ms max. (DC input)
3/2 of load power source + 1 ms max. (AC input)
1/2 of load power source + 1 ms max. (DC input)
3/2 of load power source + 1 ms max. (AC input)
1.6 V (RMS) max
5 mA max (at 100V AC)
10 mA max (at 200V AC)
600
600
-SHO5G = 100,
-SHO10G, -SH25G= 50
50
-SHO5G = 200,
-SHO10G, -SH25G= 100
100
-SHO5G = 24.5,
-SHO10G=112.5 -SH25G= 260
1260
125
100 MΩ min (at 500 VDC)
2,500V AC, 50/60 Hz for 1 minute
10…55 Hz, 1.5 mm double amplitude (10 G)
1,000 m/s2 (100 G)
1.8 V (RMS) max
10 mA max. (@ 200V AC)
20 mA max. (@ 400V AC)
1200
100
300
260, SH40 = 1800
Operating: -30°C…80°C (-22°F…176°F) with no icing or condensation
Storage: -30°C…100°C (-22°F…212°F) with no icing or condensation
Approx. 60g
Operating: 45%…85% (no condensation)
UL508, CSA C22.2, CE, TÜV
Approx. 70g
Approx. 80g
➊ Cat. No. 700-SH_ _ _HZ25 not CE or TÜV approved.
Inrush Current Resistivity➋
➌
➋ Inrush current resistivity is the ability of an SSR to withstand a large surge current for a short period of time. Surges are considered non-repetitive (max. repeatability
once every 2…5 seconds). Keep the inrush current to half the rated value if it occurs repetitively. Exceeding the non-repetitive inrush current will damage the SSR.
➌ The heat sink size refers to the combined area of the sides of the heat sink that radiate heat. For example, when a current of 18 A is allowed to flow through the SSR
at 40°C, the graph shows that the heat sink size is about 450 cm2. Therefore, if the heat sink is square, one side of the heat sink must be 15 cm (152 x 2 = 450) or longer.
54