English
Language : 

700-SH Datasheet, PDF (3/7 Pages) Allen-Bradley – Solid-State Relays
Bulletin 700-SH
Solid-State Relays
Specifications
Cat. No.
700-SH_ _G…
700-SH_ _ H…
Cat. No.
700-SH05G…
700-SH10G…
700-SH10H…
700-SH25G…
700-SH25H…
700-SH40G…
700-SH40H…
Rated Control
Voltage
5...24V DC
100...120V AC
200...240V AC
5...24V DC
Rated Load
Voltage
—
24…240V AC
200…480V AC
24…240V AC
200…480V AC
24…240V AC
200…480V AC
Operating Control
Voltage Range
4...32V DC
75...132V AC
150…264V AC
4…32V DC
Load Voltage
Range
—
19 …264V AC
180…528 VAC
19…264V AC
180…528V AC
19…264V AC
180…528V AC
Control/Input Ratings
Impedance ➊
Control Voltage Levels
15 mA max ➋
Pick-up Voltage
4V DC max.
36 kΩ +/-20%
75V AC max. ➌
72 kΩ +/-20%
150V AC max. ➌
5 mA max. ➋
4V DC max.
Load/Output Ratings
Applicable Load
Continuous Load
Current (Resistive)
With Heat Sink (A) ➍
Without Heat Sink (A) ➍
Min.
Max.
Min.
Max.
0.1 A
5A
0.1 A
3A
0.1 A
10 A
0.1 A
4A
0.2 A
10 A
0.2 A
4A
0.1 A
25 A
0.1 A
4A
0.2 A
25 A
0.2 A
4A
0.1 A
40 A
0.1 A
6A
0.2 A
40 A
0.2 A
6A
Drop-out Voltage
1V DC min.
20V AC min. ➌
40V AC min. ➌
1V DC min.
Max. Inrush Current➎
60 A (@50/60 Hz, 1 cycle)
150 A (@50/60 Hz, 1
cycle)
220 A (@ 50/60 Hz, 1
cycle)
440 A (@ 50/60 Hz, 1
cycle)
➊ The input impedance is measured at the maximum value of the rated supply voltage.
➋ With a constant current input system, SSR impedance varies with a change in input voltage.
➌ Refer to graphs, “Temperature Characteristics…” and “Must Release Voltage” on page 54 for further details.
➍ When specified heat sink is used. Refer to accessories, page 52 for applicable heat sinks. For more details, refer to graphs “Load Current Vs. Ambient Temperature
Characteristics” on page 55, and the “Heat Sink vs. Load Current” graph on page 54.
➎ If the SSR operation is continuous ON/OFF, this value should be reduced by 50%. Refer to “Inrush Current Resistivity” graphs on page 54 for more details.
53