English
Language : 

AD9516-3_15 Datasheet, PDF (38/80 Pages) Analog Devices – 14-Output Clock Generator with Integrated 2.0 GHz VCO
AD9516-3
Data Sheet
The holdover function senses the logic level of the LD pin as a
condition to enter holdover. The signal at LD can be from the
DLD, ALD, or current source LD mode. It is possible to disable
the LD comparator (Register 0x01D[3]), which causes the holdover
function to always sense LD as high. If DLD is used, it is possible
for the DLD signal to chatter some while the PLL is reacquiring
lock. The holdover function may retrigger, thereby preventing
the holdover mode from ever terminating. Use of the current
source lock detect mode is recommended to avoid this situation
(see the Current Source Digital Lock Detect section).
Once in holdover mode, the charge pump stays in a high
impedance state as long as there is no reference clock present.
As in the external holdover mode, the B counter (in the N
divider) is reset synchronously with the charge pump leaving the
high impedance state on the reference path PFD event. This
helps align the edges out of the R and N dividers for faster settling
of the PLL and to reduce frequency errors during settling. Because
the prescaler is not reset, this feature works best when the B and
R numbers are close because this results in a smaller phase
difference for the loop to settle out.
After leaving holdover, the loop then reacquires lock and the
LD pin must charge (if Register 0x01D[3] = 1) before it can
re-enter holdover (CP high impedance).
The holdover function always responds to the state of the
currently selected reference (Register 0x01C). If the loop loses
lock during a reference switchover (see the Reference Switchover
section), holdover is triggered briefly until the next reference
clock edge at the PFD.
The following registers affect the internal/automatic holdover
function:
• Register 0x018[6:5], lock detect counter. These bits change
the number of consecutive PFD cycles with edges inside the
lock detect window that are required for the DLD indicator
to indicate lock. This impacts the time required before the
LD pin can begin to charge as well as the delay from the end
of a holdover event until the holdover function can be
reengaged.
• Register 0x018[3], disable digital lock detect. This bit must
be set to a 0 to enable the DLD circuit. Internal/automatic
holdover does not operate correctly without the DLD function
enabled.
• Register 0x01A[5:0], lock detect pin output select. Set these
bits to 000100b for the current source lock detect mode if
using the LD pin comparator. Load the LD pin with a
capacitor of an appropriate value.
• Register 0x01D[3], enable LD pin comparator. 1 = enable,
0 = disable. When disabled, the holdover function always
senses the LD pin as high.
• Register 0x01D[1], enable external holdover control.
• Register 0x01D[0] and Register 0x01D[2], holdover
function enable. If holdover is disabled, both external and
internal/automatic holdover are disabled.
For example, to use automatic holdover with the following:
• Automatic reference switchover, prefer REF1
• Digital lock detect: five PFD cycles, high range window
• Automatic holdover using the LD pin comparator
Set the following registers (in addition to the normal PLL registers):
• Register 0x018[6:5] = 00b; lock detect counter = five cycles.
• Register 0x018[4] = 0b; lock detect window = high range.
• Register 0x018[3] = 0b; DLD normal operation.
• Register 0x01A[5:0] = 000100b; current source lock detect
mode.
• Register 0x01B[7:0] = 0xF7; set REFMON pin to status of
REF1 (active low).
• Register 0x01C[2:1] = 11b; enable REF1 and REF2 input
buffers.
• Register 0x01D[3] = 1b; enable LD pin comparator.
• Register 0x01D[2]=1b; enable the holdover function.
• Register 0x01D[1] = 0b; use internal/automatic holdover
mode.
• Register 0x01D[0] = 1b; enable the holdover function.
(VCO calibration must be complete before this bit is
enabled.)
• Connect REFMON pin to REFSEL pin.
Frequency Status Monitors
The AD9516 contains three frequency status monitors that are
used to indicate if the PLL reference (or references in the case of
single-ended mode) and the VCO have fallen below a threshold
frequency. A diagram showing their location in the PLL is
shown in Figure 54.
The PLL reference frequency monitors have two threshold
frequencies: normal and extended (see Table 16). The reference
frequency monitor thresholds are selected in Register 0x01B[7:5].
Frequency monitor status can be found in Register 0x01F[3:1].
Rev. C | Page 38 of 80