English
Language : 

HDS1500 Datasheet, PDF (3/6 Pages) XP Power Limited – AC-DC Power Supplies
HDS1500 Series
General
Characteristic
Efficiency
Isolation: Input to Output
Input to Ground
Output to Ground
Switching Frequency
Power Density
Signals and Controls
Mean Time Between Failure
Weight
Environmental
Characteristic
Operating Temperature
Storage Temperature
Cooling
Humidity
Vibration
Derating Curve
Thermal Derating Curve
Minimum
89
3000
1500
500
40
Minimum
-25
-40
20
Typical
65
115
5.7 (2.6)
Typical
100
80
60
40
20
-20 0 10 20 30 40 50 60 70
AmbienAt Temperature (˚C)
AC-DC Power Supplies
Maximum
93
200
9.7
Maximum
60
+85
90
2
Units
%
VAC
VAC
VAC
kHz
kHz
W/in3
kHrs
lb (kg)
Notes & Conditions
See Models and Ratings table
PFC
PWM, variable
Enable, Current Share, V Program, I Program, 5 V
Standby, Power OK
MIL-HDBK-217F, 25 °C GB
Units
°C
°C
%RH
g
Notes & Conditions
Derate linearly from 100% load at 50 °C to 60%
load at 60 °C
Internal fan fitted, speed increases with load and
internal temperature
10-500 Hz, 10 min/cycle, 60 min period for each
axis, compliant to IEC68-2-16, IEC 68-2-64
Input Derating Curve
100
90
80
70
60
50
40
90
100
110
120
264
Input Voltage (VAC)
3
www.xppower.com