English
Language : 

BCS Datasheet, PDF (3/4 Pages) XP Power Limited – DC Standby System
Models and Ratings
Output Power
155 W
Output 1
Voltage
Current(1)
13.8 V
27.6 V
13.8 V
27.6 V
11.2 A
5.6 A
10.1 A
5.1 A
Notes
1. Total power must not exceed the output power rating.
Output 2
Voltage
Current(1)
13.8 V
27.6 V
13.8 V
27.6 V
3.88 A
2.10 A
3.88 A
2.10 A
Mechanical Details
0.52
(13.15)
1.57 (4.0)
4.61 (117.0)
Output 3
Voltage
Current(1)
5.0 V
5.0 V
3.0 A
3.0 A
BCS155
Efficiency
86%
86%
85%
85%
Model Number
BCS155PS13-C
BCS155PS27-C
BCS155PS13-CA
BCS155PS27-CA
0.71
(18.0)
3-M3
3.86
(98.0)
1.38
(35.0)
7.05 (179.0)
6.77 (172.0)
0.77
(19.5)
ø0.14 (ø3.5)
V.Adj
CN2 1
0.20 (5.00)
0.20
(5.00)
0.27 (6.75)
0.35
56.0 (9.0)
(2.20)
2-M4
38.0
(1.5)
2.56 (65.0)
6.71 (170.5)
51.5 (2.03)
0.26 (6.5)
0.35
(9.0)
ø0.14 (ø3.5)
CN1 - Input/Output Connector
Pin
Function
Pin
1
Line
5
Function
+Vout
2
Neutral
6
BAT+
3
FG
7
BAT-
4
-Vout Com
8
+5V
(-A versions only)
CN2 - Alarm Connector for BCS, BCS-C
Pin
Function
1
AC OK
2
BAT LOW
3
13.8 V/20 mA or 27.6 V/20 mA
(Output voltage dependant)
CN2 - Alarm Connector for BCS-A, BCS-CA
Pin
Function
12
AC OK
34
BAT LOW
Notes
1. All dimensions in inches (mm).
2. BCS-C CN2 Mating Part JST XHP-3 housing, SXH-001 T-P0.6 crimps
or equivalent.
Derating Curves
3. BCS-CA CN2 mating part JST XHP-4 housing, SXH-001
T-P0.6 crimps or equivalent.
4. For correct operation of the internal battery fuse, the BAT- terminal should not
be connected to earth or -Vout Com.
Load vs Temp.
100
80
60
40
20
-20 0
10 20 30 40 50 60 70 (Horizontal)
Ambient Temperature (°C)