BCS Datasheet, PDF (1/4 Pages) XP Power Limited – DC Standby System | |||
|
75/100/155 Watts
BCS Series
xppower.com
⢠DC Standby System
⢠Battery Charging Output
⢠Optional 5 V, 3 A Supply
⢠Low Battery Disconnect
⢠AC OK and Battery Low Alarms
⢠Battery Overload & Reverse Polarity Protection
⢠3 Year Warranty
Specification
Input
Input Voltage
Input Frequency
Input Current
Inrush Current
Earth Leakage Current
Power Factor
Input Protection
⢠90-264 VAC (120-370 VDC)
⢠47-63 Hz
⢠75 W: 1.5/1.0 A max 115/230 VAC
100 W: 2.0/1.2 A max 115/230 VAC
155 W: 2.5/1.5 A max 115/230 VAC
⢠75/100 W 70 A max/230 VAC cold start 25 °C,
155 W 80 A max/230 VAC cold start 25 °C
⢠<1 mA at 264 VAC, 60 Hz
⢠Meets EN61000-3-2, class A
⢠Internal 4.0 A (155 W: 5.0 A) 250 V fuse,
fitted in line
Output
Output Voltage
⢠See tables
Output Voltage Trim
⢠±10% on output 1. Output 2 tracks by
same percentage
Initial Set Accuracy ⢠±1.0%
Minimum Load
⢠None
Start Up Delay
⢠75/100 W: 800 ms O/P 1 & 3, 3.5 s O/P 2,
155 W: 4 s O/P 1 & 3, 6.2 s O/P 2
Start Up Rise Time
⢠30 ms max
Hold Up Time
⢠8 ms min at 115 VAC
Line Regulation
⢠±0.5% max
Load Regulation
⢠Output 1 & 2: ±0.5%, Output 3: ±1.5%
(where fitted)
Over/Undershoot
⢠5% max at turn on
Transient Response
⢠4% max. deviation, recovery to less than
1% within 500 µs for step load change of
25%
Ripple & Noise
⢠Output 1: 1% pk-pk, Output 2: 150 mV
pk-pk, Output 3: 100 mV pk-pk (where
fitted), 20 MHz bandwidth
Overvoltage Protection ⢠115-150% on output 1 only, recycle mains
to reset
Overload Protection
⢠Output 1: >110% of total rated power
Output 2: 100-115% of max current
Output 3: >3.3 A (where fitted)
An overload on any output will affect the
voltage regulation of all outputs
Batt. Low Voltage
Protection
⢠Internal battery relay opens at 10 V±4%
for 13 V versions and 20 V±5% for 27 V
versions
Short Circuit Protection ⢠On all outputs, trip and restart, auto recovery
Temp. Coefficient
⢠0.03%/°C
General
Efficiency
Isolation
Switching Frequency
Power Density
Signals
MTBF
⢠See tables
⢠3000 VAC Input to Output
1500 VAC Input to Ground
500 VAC Output to Ground
⢠75 W: 40-76 kHz at full load typical
100 W: 28-60 kHz at full load typical
155 W: PFC 100 kHz, PWM 30-47 kHz at
25-100% load typical
⢠75 W: 3.4 W/In3,100 W: 4.5 W/In3,
155 W: 3.8 W/In3
⢠AC OK and BAT LOW signals,
see applications note
⢠130 kHrs typical to MIL-HDBK-217F
at 25 °C, GB
Environmental
Operating Temperature ⢠-20 °C to +70 °C. Refer to derating curves
Cooling
⢠75 & 100 W: Convection-cooled,
155 W: Internal fan
Operating Humidity ⢠95% RH, non-condensing
Storage Temperature ⢠-40 °C to +85 °C
Operating Altitude
⢠2000 m
Shock
⢠30 g pk, half sine, 6 axes
Vibration
⢠2 g rms, 10 Hz to 500 Hz, 10 min/cycle for
60 mins on each axis
EMC & Safety
Emissions
Harmonic Currents
Voltage Flicker
ESD Immunity
Radiated Immunity
EFT/Burst
Surge
Conducted Immunity
Dips & Interruptions
Safety Approvals
⢠EN55022, Level B conducted and radiated
⢠EN61000-3-2, class A
⢠EN61000-3-3
⢠EN61000-4-2, level 3 Perf Criteria A
⢠EN61000-4-3, 3 V/m Perf Criteria A
⢠EN61000-4-4, level 2 Perf Criteria A
⢠EN61000-4-5, installation class 3,
Perf Criteria A
⢠EN61000-4-6, 3 V Perf Criteria A
⢠EN61000-4-11, 30% 10 ms, 60% 100 ms,
100% 5000 ms, Perf Criteria A, B, B
⢠EN60950-1, UL60950-1
|
▷ |