English
Language : 

BCC200PS03 Datasheet, PDF (2/2 Pages) XP Power Limited – AC-DC Power Supplies
Models and Ratings
Output
Power
165 W
200 W
210 W
240 W
264 W
400 W
405 W
408 W
405 W
396 W
408 W
406 W
Output
Voltage
3.3 V
5.0 V
7.5 V
12.0 V
3.3 V
5.0 V
7.5 V
12.0 V
15.0 V
18.0 V
24.0 V
28.0 V
Notes
1. For -40 ºC operating temperature, add suffix ‘L’ to model number.
2. For conformally coated option, add suffix ‘E’ to model number.
Output
Current
50.0 A
40.0 A
28.0 A
20.0 A
80.0 A
80.0 A
54.0 A
34.0 A
27.0 A
22.0 A
17.0 A
14.5 A
Output
Load Regulation
1.5%
1.5%
1.5%
1.5%
1.5%
1.5%
1.5%
1.0%
1.0%
1.0%
1.0%
1.0%
BCC
Model
Number(1,2)
BCC200PS03
BCC200PS05
BCC200PS07
BCC200PS12
BCC400PS03
BCC400PS05
BCC400PS07
BCC400PS12
BCC400PS15
BCC400PS18
BCC400PS24
BCC400PS28
Mechanical Details
127.0
114.5
Overall height
1.90 (48.5)
3
81.5
1
A = 0.18 ” (4.5 mm) mounting holes for M4
50.0
Centers
55.5
Centers
47.5
Centers
TOP VIEW
59.3
Centers
–
Output
+
Output
Output Set DC OK
PL1 PL2
11
Input:
AMP Mate'n'lok 3 way.
Mating housing AMP 350766-1.
Socket crimp AMP 926893-1.
Pin 3: Live
121.5
Pin 2: Earth
Pin 1: Neutral
Output:
Power output +ve and -ve by M6 studs.
Use appropriate ring terminals and wire for the load current.
Signal connections on two 0.1 (2.5) headers (PL1 & PL2).
Mating Housing: Molex 22-01-2065.
Mating Crimp: Molex 08-50-0032.
12.5
0.0
A
48.5
Overall dimensions are 32.0
in inches (mm)
Weight:
6.0
2.87 lbs (1.3 kg)
0.0
A
A
A
Overall length 9.21 (234.0)
66
A
Pin
5.5
0.0
1
2
3
4
5
6
PL1&2 Connections
Function
Current Balance
Voltage Balance
Trim
-Remote Sense
+Remote Sense
Remote On/Off
22.0 Accessories
1. Input & output connector kit - order part ‘BCC CONKIT’.
0.0 2. For thermal pad, order part ‘BCC THERM’.
Application Notes
Current and voltage balance pins are used to connect units in parallel - see drawing.
Examples of parallel operation
Remote On/Off: Output is on with pin left floating, pull pin down to -Output to turn
output off.
+VOUT
+S
VB
Remote sense pins are used to compensate for lead drops, for up to 0.5 V maximum.
TRM
CB
When not used, move switch SW1 to local positions. See below for switch positions.
-S
The BCC series is approximately 80% efficient, so for 400 W load consumption,
-VOUT
the cooling system used will have to be able to absorb 100 W while maintaining the
baseplate to a maximum of +83 °C.
+VOUT
+S
Remote sense switchers - single unit
VB
TRM
Load
SW1 D (1)
SW1 C (2)
Remote
OFF
OFF
Local
ON
ON
CB
-S
-VOUT
SW1 B (3)
ON
OFF
SW1 A (4)
ON
OFF
+VOUT
+S
VB
Parallel units with remote sense
Parallel units without remote sense
TRM
PSU 1 PSU 2 PSU 3
PSU 1 PSU 2 PSU 3
CB
SW1 D (1) OFF
OFF
OFF
SW1 C (2) OFF
OFF
OFF
SW1 D (1) ON
SW1 C (2) ON
OFF
OFF
OFF
OFF
-S
-VOUT
SW1 B (3) ON
OFF
OFF
SW1 B (3) OFF
OFF
OFF
Ensure output power leads are of equal length and type for all
SW1 A (4) ON
OFF
OFF
SW1 A (4) OFF
OFF
OFF
units and that they are capable of carrying the load current. Set all
units to the required output ±0.1V. The voltage setting pot on unit
Contact sales office for a full set of application notes.
1 can be used to set the overall output voltage if required.
13-Nov-07