CPB1KPS3V3 Datasheet, PDF (1/3 Pages) XP Power Limited – AC-DC Power Supplies | |||
|
660 - 1680 Watts
CPB1K/1K5 Series
xppower.com
⢠Universal PFC Input
⢠Low Profile (61 mm)
⢠Wide Output Voltage Adjustment
⢠Remote On/Off
⢠Power Good Signal
⢠Remote Sense
⢠Peak Current Available
Specification
Input
Input Voltage
⢠85-264 VAC (120-370 VDC)
Input Frequency
⢠47-63 Hz
Input Current
⢠19 A at 115 VAC
Inrush Current
⢠40 A at 230 VAC
Power Factor
⢠0.98/0.95 at 115/230 VAC
Earth Leakage Current ⢠1.5 mA max at 230 VAC/60Hz
Output
Output Voltage
⢠See tables
Output Voltage Trim ⢠See tables
Minimum Load
⢠No minimum load required
Start Up Time
⢠400 ms typical at 230 VAC, 100% load
Hold Up Time
⢠20 ms typical at 100% load
Drift
⢠±0.4% max
Line Regulation
⢠±0.5% max
Load Regulation
⢠±1.0% max 0-100% load
Ripple & Noise
⢠±1.0% pk-pk, 20MHz BW
Overvoltage Protection ⢠110-130% Vnom, recycle input to reset
Overtemperature
Protection
⢠Operates in the event of fan failure or if
the operating temperature / derating
criteria is exceeded
Overload Protection
⢠Operates at 105% of rated current (101%
of pk rating), <5 s auto recovery,
>5 s recycle input to reset
Temperature
Coefficient
⢠±1.25% max -20 ºC to +50 ºC
Remote Sense
⢠Compensates for up to 0.3 V drop max
if not required, sense teminals must be
connected locally i.e +S to +M and
-S to -M on CN1
Remote On/Off
⢠12 V 3 mA applied between RCG &
RC2 will inhibit the output of the unit
and the fan
General
Efficiency
Isolation
Switching Frequency
⢠See tables
⢠3000 VAC Input to Output
2000 VAC Input to Ground
500 VAC Output to Ground
⢠130 kHz PFC, 200 kHz PWM
Environmental
Operating Temperature ⢠-20 ºC to +70 ºC, derate linearly from
+50 ºC to 50% at +70 ºC
Relative Humidity
⢠20-90% non-condensing
Storage Temperature ⢠-20 ºC to +75 ºC
Shock
⢠20 G 11 ms, once each x, y and z axis
Vibration
⢠2 G, 10 Hz to 55 kHz, 3 min periods for 60
min along each x, y and z axis
EMC & Safety
Emissions
ESD Immunity
Radiated Immunity
EFT/Burst
Surge
Safety Approvals
⢠EN55022, level B conducted
EN55022, level A radiated
⢠EN61000-4-2, level 2 contact, level 3 air
⢠EN61000-4-3, level 3
⢠EN61000-4-4, level 3
⢠EN61000-4-5, level 3 line to line,
level 4 line to ground
⢠EN60950, UL60950, cUL (CSA 60950)
|
▷ |