English
Language : 

EN1C11_15 Datasheet, PDF (2/13 Pages) Vicor Corporation – Component Power Front-end System for EN Compliance
EN1xxx
ELECTRICAL CHARACTERISTICS
Electrical characteristics apply over the full operating range of input voltage, output power and baseplate temperature, unless otherwise
specified. All temperatures refer to the operating temperature at the center of the baseplate. Performance specifications are based on the
ENMod system as shown in Figure 1a.
INPUT SPECIFICATIONS (see Figure 3 thru Figure 7 for operating characteristics)
Parameter
Min
Typ
Max
Unit
Notes
Operating input voltage
Low range
90
115
132
Vac
Autoranging (doubler mode)
High range
180
230
264
Vac
Autoranging (bridge mode)
Input undervoltage
90
Vac
Shutdown
AC line frequency
47
63
Hz
C-, and T-Grade
Power factor
0.68
0.72
Typical line
Inrush current
30
Amps
264 Vac line voltage
OUTPUT SPECIFICATIONS
Parameter
Min
Output power
0
Efficiency
@115 Vac
93
@ 230 Vac
96
Output voltage
250
External hold-up capacitance
Typ
Max
Unit
Notes
575
Watts
94
%
Full load
97
%
Full load
375
Vdc
1,750
µF
2-3300 µF in Series–HUB 3300S
CONTROL SPECIFICATIONS
Parameter
Min
Typ
Max
AC Bus OK (BOK)
Low state resistance
15
Low state voltage
0.1
High state voltage
14.8
15.0
15.2
BOK true threshold
235
240
245
BOK false threshold
200
205
210
Module Enable (EN)
Low state resistance
15
Low state voltage
0.1
High state voltage
12
14
16
Enable threshold
235
240
Disable threshold
185
190
195
AC Bus OK - Module Enable,
differential error*
12
14
16
*Tracking error between BUS OK and Enable thresholds
Unit
Notes
Ω
To negative output – Bus normal
Vdc
50 mA maximum
Vdc
Bus abnormal, 27 k internal pull up to 15 Vdc (see Fig.12)
Vdc
Output Bus voltage
Vdc
Output Bus voltage
Ω
To negative output – Converters disabled
Vdc
50 mA maximum
Vdc
150 k internal pull up to 15 Vdc (see Figure 11)
Vdc
Output bus voltage
Vdc
Output bus voltage
Vdc
AC Bus OK and Module Enable thresholds track
ENMODS™
Page 2 of 13
Rev 3.1
06/2015
vicorpower.com
800 927.9474