SU8000RT3U1TF_15 Datasheet, PDF (6/6 Pages) Tripp Lite. All Rights Reserved – SmartOnline 208/120V 8kVA 7.2kW On-Line Double-Conversion UPS, Extended Run, SNMP,Webcard, 8U Rack/Tower, Bypass Switch
WatchDog Compatibility
Supports Watchdog application, OS and hard-reboot restart options for remote applications
LINE / BATTERY TRANSFER
Transfer Time
Transfer Time (Economy Mode)
Low Voltage Transfer to Battery
Power (Setpoint)
High Voltage Transfer to Battery
Power (Setpoint)
No transfer time (0 ms.) in online, double-conversion mode
8 ms. typical power failure response in optional economy mode
100V
300V
SPECIAL FEATURES
Cold Start (Startup in Battery Mode
During a Power Failure)
Economy Mode Operation
High Availability UPS Features
Green Energy-Saving Features
Cold-start operation supported
Optional economy mode enables high-efficiency bypass operation with a maximum output voltage variation of
+/-10%. Double conversion mode is automatically restored as mains voltage varies beyond +/-10% with less than 1
millisecond transfer time between modes.
Automatic inverter bypass; Manual bypass switch; Detachable hot-swap PDU; Hot swappable UPS power module;
Hot swappable batteries
High efficiency economy mode operation; Schedulable daily hours of economy mode operation
CERTIFICATIONS
UPS Certifications
UPS Certification Details
Tested to UL1778 (USA); Tested to CSA (Canada); Tested to NOM (Mexico); Meets FCC Part 15 Category A (EMI)
IEC 61000-4-5 1995 B Surge Immunity
WARRANTY
Product Warranty Period (Worldwide) 2-year limited warranty
Connected Equipment Insurance
(U.S., Canada & Puerto Rico)
$250,000 Ultimate Lifetime Insurance