Nominal Voltage Details
7200 watts total output supported; 5000 watts maximum 120V output; Add 1 additional SU5000XFMRT2U
transformer for full load 120V operation; Voltage selection via front panel LCD interface; This configuration requires
the Power Module be set to 208V output voltage; Included step-down transformer supports 120V output
Frequency Compatibility
60 Hz
Frequency Compatibility Details
Output frequency regulation +/- 0.05Hz (free running)
Output Voltage Regulation (Line
Mode)
+/- 2%
Output Voltage Regulation
(Economy Line Mode)
+/- 10%
Output Voltage Regulation (Battery
Mode)
+/- 2%
Output Receptacles
(12) 5-15/20R; (4) L6-20R; (2) L6-30R
Output Circuit Breakers
20A double-pole (x2) protects 2 L6-20R outlets each, 30A double-pole (x2) protects 1 L6-30R outlets each, 20A
single-pole (x4) protect 3 5-15/20R outlets each
Output AC Waveform (AC Mode)
Pure Sine wave
Output AC Waveform (Battery Mode) Pure Sine wave
INPUT
Rated input current (Maximum Load) 44.2A (208V)
Nominal Input Voltage(s) Supported 208V AC
UPS Input Connection Type
Hardwire
UPS Input Connection Description 3 wire single phase input (L1, L2, G)
Recommended Electrical Service
50A
Input Phase
Single-Phase
BATTERY
Full Load Runtime (min.)
Half Load Runtime (min.)
Expandable Battery Runtime
External Battery Pack Compatibility
DC System Voltage (VDC)
Battery Recharge Rate (Included
Batteries)
Battery Replacement Description
5.5 min. (7200w)
13.5 min. (3600w)
Supports extended runtime with optional external battery packs
BP240V10RT3U ; BP240V557C-1PH ; BP240V787C-1PH ; BP240V1037C-1PH ; BP240V1407C-1PH
240
Less than 6 hours from 10% to 90% (typical, full load discharge)
Hot-swappable, user replaceable external battery packs
VOLTAGE REGULATION
Voltage Regulation Description
Overvoltage Correction
Undervoltage Correction
2% output voltage regulation in standard online, double-conversion mode
Corrects overvoltages up to 300V
Corrects undervoltages as low as 100V