English
Language : 

SU8000RT4U_15 Datasheet, PDF (5/6 Pages) Tripp Lite. All Rights Reserved – SmartOnline 240/208/120V 8kVA 5.6kW On-Line Double-Conversion UPS, Extended Run, SNMP,Webcard, 4U Rack-Tower, Split-Phase input, Bypass Switch
UPS Shipping Dimensions (hwd /
cm)
Shipping Weight (lbs.)
Shipping Weight (kg)
Cooling Method
UPS Housing Material
33 x 58.4 x 94
212
96.2
Fans
Steel
ENVIRONMENTAL
Operating Temperature Range
Storage Temperature Range
Relative Humidity
AC Mode BTU / Hr. (Full Load)
AC Mode Efficiency Rating (100%
Load)
Operating Elevation (ft.)
Audible Noise
Operating Elevation (m)
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
0 to 95%, non-condensing
2353.3
89%
0-3000m (0 to 10,000 ft.)
60 dBA at front side 1 meter
0-3000 m
COMMUNICATIONS
Communications Interface
USB (HID enabled); DB9 Serial; Contact closure; EPO (emergency power off); Slot for SNMP/Web interface
Network Monitoring Port Description RS232 and contact closure communications are supported on one DB9 port
PowerAlert Software
Included
Communications Cable
USB and DB9 cabling included
LINE / BATTERY TRANSFER
Transfer Time
Low Voltage Transfer to Battery
Power (Setpoint)
High Voltage Transfer to Battery
Power (Setpoint)
No transfer time (0 ms.) in online, double-conversion mode
65V (L1-N:L2-N)
140V (L1-N:L2-N)
SPECIAL FEATURES
Cold Start (Startup in Battery Mode
During a Power Failure)
High Availability UPS Features
Green Energy-Saving Features
Cold-start operation supported
Automatic inverter bypass; Manual bypass switch; Detachable hot-swap PDU; Hot swappable UPS power module;
Hot swappable batteries
High efficiency economy mode operation; Schedulable daily hours of economy mode operation
CERTIFICATIONS