SU8000RT4U_15 Datasheet, PDF (3/6 Pages) Tripp Lite. All Rights Reserved – SmartOnline 240/208/120V 8kVA 5.6kW On-Line Double-Conversion UPS, Extended Run, SNMP,Webcard, 4U Rack-Tower, Split-Phase input, Bypass Switch
Nominal Voltage Details
240/120V or 208/120V split phase output
Frequency Compatibility
60 Hz
Frequency Compatibility Details
Output frequency regulation +/- 0.05Hz (free running)
Output Voltage Regulation (Line
Mode)
+/- 3%
Output Voltage Regulation
(Economy Line Mode)
+/- 10%
Output Voltage Regulation (Battery
Mode)
+/- 3%
Output Receptacles
(4) 5-15/20R; (2) L6-20R; (2) L6-30R; Hardwire
Output Receptacle Details
Supports 208/120V or 240/120V hardwire output (L1, L2, N, G)
Output Circuit Breakers
20A branch rated breakers (x4) protect 1 5-15/20R outlet each, 20A double pole breakers (x2) protect one L6-20R
each, L6-30R outlets are unbreakered
Output AC Waveform (AC Mode)
Pure Sine wave
Output AC Waveform (Battery Mode) Pure Sine wave
INPUT
Rated input current (Maximum Load) 34A
Nominal Input Voltage(s) Supported 208V AC / 120V AC (4 wire split single phase); 240V AC /120V AC (4 wire split single phase)
UPS Input Connection Type
Hardwire
UPS Input Connection Description 4 wire split-phase input (L1, L2, N, G)
Recommended Electrical Service
40A 208/120V or 240/120V Split Phase
Input Phase
Single-Phase
BATTERY
Full Load Runtime (min.)
Half Load Runtime (min.)
Expandable Battery Runtime
External Battery Pack Compatibility
DC System Voltage (VDC)
Battery Recharge Rate (Included
Batteries)
Internal UPS Replacement Battery
Cartridge
Battery Access
Battery Replacement Description
5 min. (5600w)
12 min. (2800w)
Supports extended runtime with optional external battery packs
BP192V1037C-1PH ; BP192V12-3U ; BP192V1407C-1PH ; BP192V557C-1PH ; BP192V787C-1PH ;
BP192V5RT2U (limit 1)
192
Less than 6 hours from 10% to 80% (typical, full load discharge)
RBC9-192
Front panel battery access door
Hot-swappable, user replaceable batteries
VOLTAGE REGULATION
3/6