Frequency Compatibility Details
Output frequency matches input nominal on startup, defaults to 50 Hz on cold-start
Output Voltage Regulation (Line
Mode)
+/- 3%
Output Voltage Regulation
(Economy Line Mode)
+/- 10%
Output Voltage Regulation (Battery
Mode)
+/- 3%
Output Receptacles
(4) C13; (2) C19
Included Output Power Cables
Includes 2 C13 to C14 and 1 C20 to C19 output power cables
Load Management Receptacles
Two switchable single-outlet C19 load banks
Hot-Swap PDU options
PDUBHV20 (2U / 6 C13, 2 C19 outlets)
Output AC Waveform (AC Mode)
Sine wave
Output AC Waveform (Battery Mode) Pure Sine wave
INPUT
Rated input current (Maximum Load) 9.7A (200V), 9.3A (208V), 8.8A (220V), 8.5A (230V), 8.1A (240V)
Nominal Input Voltage(s) Supported 200V AC; 220V AC; 230V AC; 240V AC
UPS Input Connection Type
C20 inlet
UPS Input Connection Description C20 inlet accepts user-supplied AC power cord
Input Circuit Breakers
15A
Input Phase
Single-Phase
BATTERY
Full Load Runtime (min.)
Half Load Runtime (min.)
Expandable Battery Runtime
External Battery Pack Compatibility
DC System Voltage (VDC)
Battery Recharge Rate (Included
Batteries)
Internal UPS Replacement Battery
Cartridge
Battery Access
Battery Replacement Description
5 min. (1600w)
14 min. (800w)
Supports extended runtime with optional external battery packs
BP48V24-2U (limit 1); BP48V60RT-3U (multi-pack compatible); BP48V27-2US (multi-pack compatible)
48
Less than 6 hours from 10% to 80% (typical, full load discharge)
RBC94-2U
Front panel battery access door
Hot-swappable, user replaceable batteries
VOLTAGE REGULATION
Voltage Regulation Description
Overvoltage Correction
Online, double-conversion power conditioning
3% output voltage regulation during overvoltages to 275