English
Language : 

SS24D50 Datasheet, PDF (1/4 Pages) Teledyne Technologies Incorporated – Output to 75A, 510 Vac Solid-State Relay with Diagnostic
FEATURES/BENEFITS
• Zero switching AC output
• DC control input
• Fault detection: line or load open; short-circuit output
• Solid-state N.C. status output without power supply
• Control and status LED indicators
• Terminal block for control and status output connections
NEW Series SS
Output to 75A, 510 Vac
Solid-State Relay with Diagnostic
Part Number
SS24D50
SS24D75
SS48D50
SS48D75
Description
50A, 70–280 Vac with diagnostic
75A, 70–280 Vac with diagnostic
50A, 150–510 Vac with diagnostic
75A, 150–510 Vac with diagnostic
Part Number Explanation
SS
24
D
50
Series
Switch Type2
Line Voltage1 Output Current – Amps
MECHANICAL SPECIFICATION
1.063 (27)
0.898 ±0.02
(22.8 ) ±0.5
0.77
(19.6)
0.89 (28)
Ø4.7
M4
1 L1
2 T1
150–510 Vac
75A
with heat sink
control
8–32 Vdc
A2 A1
3– 4+
status
N.C. output
max 30V 0.1A
5– 6+
ELECTRICAL SPECIFICATIONS
(+25°C ambient temperature unless otherwise specified)
INPUT (CONTROL) SPECIFICATIONS
Min Max Units
Control Range
SS24
7
32
V
SS48
8
32
V
Input Current Range
SS24
SS48
4
30
mA
4
28
mA
Must Turn-Off Voltage
SS24
3
V
SS48
4
V
Input Resistance (Typical)
All relays
1000 Ohms
Reverse Voltage Protection
All relays
30
V
1.38 (35)
TOLERANCES: ±0.01 (±0.3)
WEIGHT: 3.52 oz. (100g)
Figure 1
1.14 (29)
1.75 (44.5)
BLOCK DIAGRAM
Ic A1
Control Vc 4+
3–
Vs Id A2
6+
Vds 5–
Status output
0V/Vs
green
yellow
Mains
150–510V
1 L1
Fuse
Load
2 T1
Without faults, the status output is normally closed (NC)
Figure 2
STATUS OUTPUT SPECIFICATIONS
Min Max
Supply Voltage
1
32
Output Current
0
0.1
On Resistance
2
Maximum Cable Length
40
Units
V
A
Ohms
m
© 2003 TELEDYNE RELAYS
(800) 284-7007 • www.teledynerelays.com
SS Page 1
SS/052002\Q1