Technical Specification
Input: 35-75 V
Output: 5.0 V
Current: 30 A
Package: Quarter-brick
ELECTRICAL CHARACTERISTICS (Continued)
Parameter P
Min.
Typ. Max. Units Notes & Conditions
FEATURE CHARACTERISTICS
Switching Frequency
250
280
310
kHz
ON/OFF Control (Option P)
Off-State Voltage
-2
0.8
V
On-State Voltage
2.4
18
V
ON/OFF Control (Option N)
Off-State Voltage
2.4
18
V
On-State Voltage
-2
0.8
V
ON/OFF Control (Either Option)
Pull-Up Voltage
Vin/6.5
9.2
V
Pull-Up Resistance
40
kW
Output Voltage Trim Range
-20
+10
%
Output Voltage Remote Sense Range
+10
%
Output Over-Voltage Protection
117
122
127
%
Over-Temperature Shutdown
125
°C
Over-Temperature Shutdown Restart Hysteresis
10
°C
Load Current Scale Factor
857
RELIABILITY CHARACTERISTICS
Calculated MTBF (Telcordia)
2.1
106 Hrs.
Calculated MTBF (MIL-217)
1.75
106 Hrs.
Field Demonstrated MTBF
106 Hrs.
Regulation and Isolation stage
Figures A & B
Measured across Pins 8 & 4; Figures 23 & C
Measured across Pins 8 & 4
Over full temp range; % of nominal Vout
Average PCB Temperature
See App Note: Output Load Current Calc.
TMSReI-LeN-HW oDuBTr-K0w-02e01b37s3iFt;e28;fo08r%0d%leoltaoadail,ds3,30000LLFFMM,,4400ooCCTTaa
STANDARDS COMPLIANCE
Parameter P
STANDARDS COMPLIANCE
UL/cUL 60950-1
EN60950-1
72/23/EEC
93/68/EEC
Needle Flame Test (IEC 695-2-2)
IEC 61000-4-2
GR-1089-CORE
Telcordia (Bellcore) GR-513
Notes
File # E194341, Basic insulation & pollution degree 2
Certified by TUV
Test on entire assembly; board & plastic components UL94V-0 compliant
ESD test, 8kV - NP, 15kV air - NP (Normal Performance)
Section 7 - electrical safety, Section 9 - bonding/grounding
• An external input fuse must always be used to meet these safety requirements. Contact SynQor for official safety
certificates on new releases or download from the SynQor website.
QUALIFICATION TESTING
Parameter P
QUALIFICATION TESTING
Life Test
Vibration
Mechanical Shock
Temperature Cycling
Power/Thermal Cycling
Design Marginality
Humidity
Solderability
# Units Test Conditions
32
5
5
10
5
5
5
15 pins
95% rated Vin and load, units at derating point, 1000 hours
10-55Hz sweep, 0.060” total excursion,1 min./sweep, 120 sweeps for 3 axis
100g minimum, 2 drops in x and y axis, 1 drop in z axis
-40°C to 100°C, unit temp. ramp 15°C/min., 500 cycles
Toperating = min to max, Vin = min to max, full load, 100 cycles
Tmin-10°C to Tmax+10°C, 5°C steps, Vin = min to max, 0-105% load
85°C, 85% RH, 1000 hours, 2 minutes on and 6 hours off
MIL-STD-883, method 2003
• Extensive characterization testing of all SynQor products and manufacturing processes is performed to ensure that we supply
robust, reliable product. Contact the factory for official product family qualification documents.
Product # PQ60050QTA30
Phone 1-888-567-9596
www.synqor.com
Doc.# 005-2QT650C Rev. E
05/20/09
Page 4