3RT, 3TB, 3TF Contactors for Switching Motors
3RT10 contactors, 3-pole, 3 ... 250 kW
Rated control supply voltages
Contactor type
3RT10 1
Rated control supply voltage Us
3RT10 2,
3RT10 3,
3RT10 4
3RT14 4
3RT13 1,
3RT15 1
3RT13 2 to 3RT13 4,
3RT15 2 and 3RT15 3
3RT16
Rated control supply voltages (the 10th and 11th position of the order number must be changed)
Sizes S00 ... S3
AC operation1)
Coils for 50 Hz (exception: size S00: 50 and 60 Hz2))
24 V AC
B0
B0
B0
B0
B0
42 V AC
D0
D0
D0
D0
--
48 V AC
H0
H0
H0
H0
--
110 V AC
F0
F0
F0
F0
F0
230 V AC
P0
P0
P0
P0
P0
400 V AC
V0
V0
V0
V0
V0
Coils for 50 and 60 Hz2)
24 V AC
B0
C2
C2
B0
C2
42 V AC
D0
D2
D2
D0
D2
48 V AC
H0
H2
H2
H0
H2
110 V AC
F0
G2
G2
F0
G2
220 V AC
N2
N2
N2
N2
N2
230 V AC
P0
L2
L2
P0
L2
For USA and Canada3)
50 Hz
60 Hz
110 V AC
120 V AC
K6
K6
K6
K6
K6
220 V AC
240 V AC
P6
P6
P6
P6
P6
For Japan
50/60 Hz4)
60 Hz5)
100 V AC
110 V AC
G6
G6
G6
G6
G6
200 V AC
220 V AC
N6
N6
N6
N6
N6
400 V AC
440 V AC
R6
R6
R6
R6
R6
DC operation1)
12 V DC
24 V DC
42 V DC
48 V DC
60 V DC
110 V DC
125 V DC
220 V DC
230 V DC
A4
--
--
A4
--
B4
B4
B4
B4
B4
D4
D4
D4
D4
D4
W4
W4
W4
W4
--
E4
E4
E4
--
--
F4
F4
F4
F4
F4
G4
G4
G4
G4
G4
M4
M4
M4
M4
M4
P4
P4
P4
P4
--
Sizes S6 ... S12
AC/DC operation (40 ... 60 Hz, DC)
Conventional operating mechanism
Us
min
...
Us
6)
max
Contactor type
23 ... 26 V AC/DC
42 ... 48 V AC/DC
110 ... 127 V AC/DC
200 ... 220 V AC/DC
220 ... 240 V AC/DC
3RT1. 5.-.A
3RT1. 6.-.A
3RT1. 7.-.A
B3
D3
F3
M3
P3
Us
min
...
Us
6)
max
240 ... 277 V AC/DC
380 ... 420 V AC/DC
440 ... 480 V AC/DC
500 ... 550 V AC/DC
575 ... 600 V AC/DC
Solid-state operating mechanism
Us
min
...
Us
6)
max
Contactor type
21 ... 27.3 V AC/DC
96 ... 127 V AC/DC
200 ... 277 V AC/DC
3RT1. 5.-.N
3RT1. 6.-.N
3RT1. 7.-.N
B3
F3
P3
3RT1. 5.-.P/Q
3RT1. 6.-.P/Q
3RT1. 7.-.P/Q
--
F3
P3
1) For deviating coil voltages and coil operating ranges of sizes S00 and S0,
the 24 V DC SITOP Power power supply with wide range input
(93 to 264 V AC; 30 to 264 V DC) can be used for coil excitation
(see Power Supplies -> SITOP Power Power Supplies).
2) Coil operating range
at 50 Hz: 0.8 to 1.1 x Us
at 60 Hz: 0.85 to 1.1 x Us
3) Coil operating range
Size S00:
at 50 Hz: 0.85 to 1.1 x Us
at 60 Hz: 0.8 to 1.1 x Us
Sizes S0 to S3: at 50 Hz and 60 Hz: 0.8 to 1.1 x Us
4) Coil operating range
Size S00:
at 50/60 Hz: 0.85 to 1.1 x Us
Sizes S0 to S3: at 50 Hz: 0.8 to 1.1 x Us
at 60 Hz: 0.85 to 1.1 x Us
5) Coil operating range
at 60 Hz: 0.8 to 1.1 x Us
6) Operating range:
0.8 x Us min to 1.1 x Us max
B0
--
--
F0
P0
V0
C2
--
--
G2
N2
L2
K6
P6
G6
N6
R6
--
--
--
--
--
--
--
--
--
Contactor type
3RT1. 5.-.A
3RT1. 6.-.A
3RT1. 7.-.A
U3
V3
R3
S3
T3
Siemens LV 1 · 2006