3RT10161BB41 Datasheet, PDF (11/70 Pages) Siemens Semiconductor Group – Controls – Contactors and Contactor Assemblies
3RT, 3TB, 3TF Contactors for Switching Motors
Control circuit:
• Contactor control through AS-Interface by way of terminals
AS-i +/AS-i –. Each of these terminals is jumpered and
connected twice to a 4-pole connector which is separate from
the other control inputs.
Advantages:
- The AS-Interface cable is not interrupted if the connector is
pulled out
- The contactor remains functional through the local control
inputs and its own 6-pole connector
• Control signals through AS-i:
- Contactor ON/OFF
• Status signals through AS-i:
- Contactor ON/OFF
- Automatic/Local control:
- Remaining lifetime (RLT)
- Signal through free input, e.g. overload relay tripped.
3RT10 contactors, 3-pole, 3 ... 250 kW
A1 A2
H1
H2
H3
SF1
SF2
AS-i
AS-i
AS-i
AS-i
L1/L+
N/L-
2
S2
S1
e.g.
Overload relay
3RB20
AS-i
NSB0_01149b
13
$ Solid-state module of
3RT1 ...-.Q contactor
% Plug-in connection, 6-pole
& Plug-in connection, 4-pole
S1 Selector switch for switching
from automatic control,
e.g. by means of AS-Interface,
to local control
S1 open: Automatic mode
S2 Local control option
Possibility of switching from automatic control to local control by
means of terminals H1/H2/H3, i.e. automatic control through
AS-Interface can be deactivated e.g. during startup or in the
event of a fault and the contactor can be controlled manually.
I/O configuration (hex)
ID code (hex)
Power supply
AS-Interface current input
Contact loading at SF1/2
Watchdog function (disconnects outputs in the event of AS-Interface fault)
Indication behavior
During operation, the LEDs on
the contactor indicate the
states shown on the right.
LED
States
AS-Interface On On
7
F
V
26.5 ... 31.6 (according to AS-Interface specification)
mA
max. 20
mA
3 ... 6
Built-in
Description of state
Flashing Flashing
Station address 0
No AS-Interface communication
AS-Interface communication OK
Contactor diagnostics using the application program
• Inputs
Input signals
DI0 "Ready"
DI1 "Running"
DI2 "Remaining lifetime"
DI3 "Free input"
Device status
0 Device not ready/manual operation
1 Device ready/automatic operation
0 Contactor off
1 Contactor on
0 Remaining lifetime RLT > 20 %
1 Remaining lifetime RLT ˆ 20 %
0 No input signal at SF1/2
1 Input signal at SF1/2
• Outputs
Output signals
DO0 "Running"
DO1
DO2
DO3
Device status
0 Contactor off
1 Contactor on
0 --
1 --
0 --
1 --
0 --
1 --
Siemens LV 1 · 2006
3/11