English
Language : 

C4P-SA21010A001000 Datasheet, PDF (6/10 Pages) SICK AG – SAFETY LIGHT CURTAINS
C4P-SA21010A001000, C4P-EA21010A001000 | deTec4 Prime
SAFETY LIGHT CURTAINS
A
B
C
D
E
F
H
I
J
K
L
M
N
O
P
Q
R
S
T
Connection diagram
deTec4 Prime safety light curtain to UE10-3OS safety relay
+24 V
s
2 +24 V
3 n.c
4 n.c.
5 In2
6 In1
1 n.c.
7 0V
8 Com1
S1
r
+24 V 2
RES 1
EDM 4
OSSD1 5
OSSD2 6
ADO 3
0V 7
Com1 8
deTec4 Prime
2)
B1 B3 Y1 13 23 33 41 1)
UE10-3OS
B2 B4 Y2 14 24 34 42
H2
0V
3) PELV
E132908/00/2015-04-07
① Output circuits. These contacts must be incorporated into the control such that the dangerous state is brought to an end if the output circuit is
open. For categories 4 and 3, they must be incorporated on two channels (x, y paths). Single-channel incorporation into the control (z path) is only
possible with a single-channel control and taking the risk analysis into account.
② To indicate the status on both sides, the Com1 connections from the sender and receiver must be connected to each other in the control cabi-
net (optional).
③ SELV/PELV safety/protective extra-low voltage.
6
OPTO-ELECTRONIC PROTECTIVE DEVICES | SICK
Online data sheet | 2017-08-21 16:38:06
Subject to change without notice