English
Language : 

PXU20030 Datasheet, PDF (31/32 Pages) Red Lion Controls. Inc – MODEL PXU - TEMPERATURE/PROCESS CONTROLLERS
REGISTER
(4x)
REGISTER NAME
LOW LIMIT
HIGH LIMIT
96 Deadband/Overlap
-99(.9) or
999(.9)° or
-999 (process) 9999 (process)
97 On/Off Control Hysteresis
2
250(.0)° or 2500
(process)
LOCKOUT PARAMETERS
101 Setpoint Access
0
4
102 Output 1 Power Access
0
4
103 Output 2 Power Access
0
4
104 Setpoint Ramp Rate Access
0
4
105 PID Group Access
0
4
106 Controller Status (Run/Stop) Access
0
4
107 Output Power Offset Access
1
3
108 Proportional band Access
1
3
109 Integral time Access
1
3
110 Derivative time Access
1
3
111 Integration Default Access
1
3
112 Alarm 1 Value Access
1
3
113 Alarm 2 Value Access
1
3
114 Alarm 3 Value Access
1
3
115 Alarm Reset Access
1
3
116 Setpoint Select Access
1
3
117 Auto-Tune Start Access
2
3
118 Auto Control Mode Access
2
3
119 Control Mode Transfer Access
2
3
120 Deviation Value Access
0
3
121 Access Code
-125
125
ALARM PARAMETERS
131 Alarm 1 Action
0
18
132 Alarm 1 Annunciator
133 Alarm 1 Reset Mode
134 Alarm 1 Standby
135 Alarm 1 Value
136 Input Fail Alarm 1 Action
0
0
0
-999
0
1
1
1
9999
1
137 Alarm 2 Action
0
18
138 Alarm 2 Annunciator
139 Alarm 2 Reset Mode
140 Alarm 2 Standby
141 Alarm 2 Value
142 Input Fail Alarm 2 Action
0
0
0
-999
0
1
1
1
9999
1
143 Alarm 3 Action
0
18
144 Alarm 3 Annunciator
145 Alarm 3 Reset Mode
146 Alarm 3 Standby
147 Alarm 3 Value
0
0
0
-999
1
1
1
9999
FACTORY
SETTING
2
2
0
1
1
1
1
0
1
1
1
1
3
1
1
1
1
1
2
2
2
0
0
0
0
0
0
100
0
0
0
0
0
200
0
0
0
0
0
300
ACCESS
COMMENTS
Read/Write
1 = 1 Display unit; In combination Reverse(r) and
Direct(d) modes, this defines the overlap area in
which both OP1 and OP2 are active
(negative value) or the deadband area (positive
value).
Read/Write 1 = 1 Display unit
Read/Write 0 = dISP, 1 = ParA, 2 = HIdE, 3 = LOC, 4 = dSPr
Read/Write 0 = dISP, 1 = ParA, 2 = HIdE, 3 = LOC, 4 = dSPr
Read/Write 0 = dISP, 1 = ParA, 2 = HIdE, 3 = LOC, 4 = dSPr
Read/Write 0 = dISP, 1 = ParA, 2 = HIdE, 3 = LOC, 4 = dSPr
Read/Write 0 = dISP, 1 = ParA, 2 = HIdE, 3 = LOC, 4 = dSPr
Read/Write 0 = dISP, 1 = ParA, 2 = HIdE, 3 = LOC, 4 = dSPr
Read/Write 1 = ParA, 2 = HIdE, 3 = LOC
Read/Write 1 = ParA, 2 = HIdE, 3 = LOC
Read/Write 1 = ParA, 2 = HIdE, 3 = LOC
Read/Write 1 = ParA, 2 = HIdE, 3 = LOC
Read/Write 1 = ParA, 2 = HIdE, 3 = LOC
Read/Write 1 = ParA, 2 = HIdE, 3 = LOC
Read/Write 1 = ParA, 2 = HIdE, 3 = LOC
Read/Write 1 = ParA, 2 = HIdE, 3 = LOC
Read/Write 1 = ParA, 2 = HIdE, 3 = LOC
Read/Write 1 = ParA, 2 = HIdE, 3 = LOC
Read/Write 2 = HIdE, 3 = LOC
Read/Write 2 = HIdE, 3 = LOC
Read/Write 2 = HIdE, 3 = LOC
Read/Write 0 = dISP, 3 = LOC
Read/Write
0 = Full access to display, parameter, hidden, and
configuration loops; -1 to -125 = Code necessary to
access configuration loop only; 1 to 125 = Code
necessary to access hidden and configuration loops
Read/Write
0 = No, 1 = AbHI, 2 = AbLO, 3 = AUHI, 4 = AULO,
5 = d-HI, 6 = d-Lo, 7 = b-In, 8 = b-ot, 9 = InPt,
10 = Ct1, 11 = Ct2, 12 = SOAK, 13 = r-UP,
14 = r-dn, 15 = rUn, 16 = HoLd, 17 = StoP, 18 = End
Read/Write 0 = Normal, 1 = Reverse
Read/Write 0 = Automatic, 1 = Latched
Read/Write 0 = No, 1 = Yes
Read/Write 1 = 1 Display unit
Read/Write 0 = Off; 1 = On
Read/Write
0 = No, 1 = AbHI, 2 = AbLO, 3 = AUHI, 4 = AULO,
5 = d-HI, 6 = d-Lo, 7 = b-In, 8 = b-ot, 9 = InPt,
10 = Ct1, 11 = Ct2, 12 = SOAK, 13 = r-UP,
14 = r-dn, 15 = rUn, 16 = HoLd, 17 = StoP, 18 = End
Read/Write 0 = Normal, 1 = Reverse
Read/Write 0 = Automatic, 1 = Latched
Read/Write 0 = No, 1 = Yes
Read/Write 1 = 1 Display unit
Read/Write 0 = Off; 1 = On
Read/Write
0 = No, 1 = AbHI, 2 = AbLO, 3 = AUHI, 4 = AULO,
5 = d-HI, 6 = d-Lo, 7 = b-In, 8 = b-ot, 9 = InPt,
10 = Ct1, 11 = Ct2, 12 = SOAK, 13 = r-UP,
14 = r-dn, 15 = rUn, 16 = HoLd, 17 = StoP, 18 = End
Read/Write 0 = Normal, 1 = Reverse
Read/Write 0 = Automatic, 1 = Latched
Read/Write 0 = No, 1 = Yes
Read/Write 1 = 1 Display unit
31