PXU11AE0 Datasheet, PDF (29/32 Pages) Red Lion Controls. Inc – MODEL PXU - TEMPERATURE/PROCESS CONTROLLERS
PXU MODBUS REGISTER TABLE
09/04/2015
The following is an example of the necessary query and corresponding response for holding register 2. In this example register 2 is the decimal value 123.
Query: 01 03 00 01 00 01 D5 CA
Response: 01 03 02 00 7B F8 67
Notes:
1. The PXU registers can be read as holding (4x) or input (3x) registers.
2. The PXU should not be powered down while parameters are being changed. Doing so may result in an in-complete write to the non-volatile memory and produce
checksum errors.
REGISTER
(4x)
REGISTER NAME
FREQUENTLY USED REGISTERS
1
Process Value (PV)
2
Active Setpoint (SP)
3
Setpoint 1 (SP1)
4
Setpoint 2 (SP2)
5
Setpoint Deviation
6
Alarm 1 Value
7
Alarm 2 Value
8
Alarm 3 Value
9
Output Power 1
10 Output Power 2
11
PB Proportional band (Active)
12 Integral time (Active)
13 Derivative time (Active)
14 Integration default (Active)
15 PID parameter set selection
16 Auto-Tune Start
17 Control Mode Transfer (Auto/Manual)
18 Controller Status
19 Setpoint Select
20 SP Ramp Rate
LOW LIMIT
N/A
-999
-999
-999
N/A
-999
-999
-999
0
0
1
0
0
0
0
0
0
0
0
0
21 LED Status
N/A
22 Pushbutton Status
N/A
23 Alarm Reset
0
24 Setpoint Ramping Disable
0
25 Integral Action Disable
0
PID PARAMETERS
33 Proportional band 1
1
34 Integral time 1
0
35 Derivative time 1
0
36 Integration default 1
0
37 Proportional band 2
1
38 Integral time 2
0
39 Derivative time 2
0
40 Integration default 2
0
41 Output Power Offset
0
HIGH LIMIT
FACTORY
SETTING
ACCESS
COMMENTS
N/A
9999
9999
9999
N/A
9999
9999
9999
1000
1000
999(.9)° or
9999 (process)
9999
9999
1000
1
1
1
1
1
999(.9)° or
9999 (process)
N/A
N/A
7
1
1
N/A
Read Only 1 = 1 Display unit
0
Read/Write 1 = 1 Display unit
0
Read/Write 1 = 1 Display unit
0
Read/Write 1 = 1 Display unit
N/A
Read Only 1 = 1 Display unit
100
Read/Write 1 = 1 Display unit
200
Read/Write 1 = 1 Display unit
300
Read/Write 1 = 1 Display unit
0
Read/Write 1 = 0.1%; writable when in manual mode only.
0
Read/Write 1 = 0.1%; writable when in manual mode only.
70
Read/Write 1 = 1 Display unit
120
Read/Write 1 = 1 second
30
Read/Write 1 = 1 second
0
Read/Write 1 = 0.1 % output power
0
Read/Write 0 = PID Set 1, 1 = PID Set 2
0
Read/Write 0 = No; 1 = Yes
0
Read/Write 0 = Automatic (PID), 1 = User (Manual Mode)
1
Read/Write 0: Stop, 1: Run
0
Read/Write 0 = SP1, 1 = SP2
0
Read/Write 1 = 1 Display unit/minute; 0 = Ramping disabled
Bit State: 0 = Off, 1 = On
N/A
Read Only b7: AT, b6:OUT1, b5: OUT2, b4: ALM1, b3: °C, b2:
°F, b1: ALM2, b0: ALM3
Bit State: 0 = Key pressed, 1 = Key not pressed
N/A
Read Only b7: D, b6: Up, b5: F1, b4: N/A, b3: P, b2: Down, b1:
F2, b0: N/A
Bit State: 1 = reset alarm, bit is returned to zero
0
Read/Write following reset
b3: Reset Alm3, b1: Reset Alm2, b0: Reset Alm1
0
Read/Write 0 = Enabled, 1 = Disabled
0
Read/Write 0 = Enabled, 1 = Disabled
999(.9)° or
9999 (process)
9999
9999
1000
999(.9)° or
9999 (process)
9999
9999
1000
1000
70
Read/Write 1 = 1 Display unit
120
Read/Write 1 = 1 second
30
Read/Write 1 = 1 second
0
Read/Write 1 = 0.1 %
70
Read/Write 1 = 1 Display unit
120
Read/Write 1 = 1 second
30
Read/Write 1 = 1 second
0
Read/Write 1 = 0.1 %
500
Read/Write 1 = 0.1 % output power
29