7.4 MODULE 4 - Alarm Parameters (4-AL) (Optional)
4-AL
P
PARAMETER MENU
ACt1 Lit1 rSt1
ALARM 1
ACTION
ALARM 1
ANNUNCIATOR
ALARM 1
RESET
MODE
Stb1
ALARM 1
STANDBY
AL-1
ALARM 1
VALUE
1FA1
INPUT FAIL
ALARM 1
ACTION
Act2 Lit2 rSt2
ALARM 2
ACTION
ALARM 2
ANNUNCIATOR
ALARM 2
RESET
MODE
Stb2
ALARM 2
STANDBY
AL-2
ALARM 2
VALUE
CNFP
P
IFA2
INPUT FAIL
ALARM 2
ACTION
Programming/model dependent.
ACt3 Lit3 rSt3
ALARM 3
ACTION
ALARM 3
ALARM 3
ANNUNCIATOR RESET
MODE
Stb3
ALARM 3
STANDBY
AL-3
ALARM 3
VALUE
IFA3 AHYS
INPUT FAIL
ALARM
ALARM 3 HYSTERESIS
ACTION
Colr
CHANGE
DISPLAY
COLOR
AVAILABLE ALARM ACTIONS
 None
No action, the remaining Alarm
parameters are not available.
 Absolute High
(balanced hysteresis)
The alarm energizes when the Process
Value exceeds the alarm value + 1/2 the
hysteresis value.
 Absolute Low
(balanced hysteresis)
The alarm energizes when the Process
Value falls below the alarm value -1/2 the
hysteresis value.
 Absolute High
The alarm energizes when the Process
(unbalanced hysteresis) Value exceeds the alarm value.
 Absolute Low
The alarm energizes when the Process
(unbalanced hysteresis) Value falls below the alarm value.
 Deviation High
 Deviation Low
 Band Acting (inside)
 Band Acting (outside)
The alarm value tracks the Setpoint value
The alarm value tracks the Setpoint value
The alarm value tracks the Setpoint value
The alarm value tracks the Setpoint value
ALARM ACTION FIGURES
AL + ½Hys
AL
AL - ½Hys
AL + Hys
SP
Hys
Hys
Hys
AL
SP - AL
ALARM
STATE
OFF
ON
OFF
TRIGGER POINTS
AbHI - AbsAoblsuotlueteHHiigghhAActicngtin(Bgala(nBceadlaHnysc)ed Hys)
ALARM
STATE
OFF
ON
OFF
TRIGGER POINTS
AuLO - AbsAoblsuotlueteLLoowwAActcintgin(gUn(bUalnanbcaedlaHnycse) d Hys)
ALARM
STATE
OFF
ON
OFF
TRIGGER POINTS
d-LO - DevDieavitaitoionn LLowoAwctinAgc(AtiLn>g0)(AL>0)
AL + ½Hys
AL
Hys
AL - ½Hys
ALARM
STATE
OFF
ON
OFF
TRIGGER POINTS
AbLO - AbsAoblsuoltuete LoowwAcAtincgti(nBagla(nBceadlHayns)ced Hys)
SP + AL
Hys
SP
ALARM
STATE
OFF
ON
OFF
TRIGGER POINTS
d-HI - DevDieavtiaiotionn HHighigAchtinAg (cAtLi>n0g) (AL>0)
SP + AL
Hys
SP
SP - AL
Hys
ALARM
STATE
ON
OFF
ON
OFF ON
TRIGGER POINTS
b-INBa-ndInInssiiddeeAActicngting
AL
SP
Hys
SP + (-AL)
AL - Hys
Hys
ALARM
STATE
OFF
ON
OFF
ALARM
STATE ON
OFF
ON
TRIGGER POINTS
AuHI - AbsAobsloulutete HHigihgAhctiAngc(tUinnbgala(nUcendbHaysl)anced Hys)
TRIGGER POINTS
d-HI - DeDveviaiattiioonnHiHghigAchtinAgc(AtiLn<g0)(AL<0)
Note: Hys in the above figures refers to the Alarm Hysteresis.
SP + AL
Hys
SP
SP - AL
Hys
ALARM OFF ON
STATE
OFF
ON OFF
TRIGGER POINTS
b-ot - BaBnadndOOuutstisdeidAectinAgcting
17