RACD12-LP Datasheet, PDF (2/4 Pages) Recom International Power – Terminal Block Input/Output with Cable Clamps
RACD12-LP
AC/DC Converter
Specifications (measured @ ta= 25°C, 240VAC and rated load)
Series
PROTECTION
Parameter
Input Fuse
Open Circuit Protection (OCP)
Over Load Protection (OLP)
Over Voltage Protection (OVP)
Over Temperature Protection (OTP)
Isolation Voltage
Condition
external fuse is recommended
110°C Tcase
I/P to O/P
Maximum loading of automatic circuit breakers
@ 230VAC, 1Ohm, 90° phase angle and max. load
Circuit Breaker
Circuit Breaker Current
Typ
10A
16A
20A
25A
B
17
28
35
44
C
37
59
74
92
Value
T1A
auto recovery after fault condition is removed
auto recovery after fault condition is removed
auto recovery after fault condition is removed
auto recovery after fault condition is removed
3.75kVAC / 1 minute
ENVIRONMENTAL
Parameter
Operating Temperature Range
Maximum Case Temperature
Operating Altitude
Operating Humidity
IP Rating
Pollution Degree
Design Lifetime
Derating Graph
Condition
100
80
60
40
20
0
-20 -10 0 10 20 30 40 50 60
Ambient Temperature [°C]
Value
-20°C to +50°C, Ambient
+80°C
2000m
5% to 85% RH, non condensing
IP20
PD2
30 x 10³ hours
SAFETY AND CERTIFICATIONS
Certificate Type
Lamp Controlgear General Requirments for Safety
Lamp Controlgear Particular Requirements
D.C. or A.C. Controlgears for LED Performance Requirements
RoHS 2.1
L-2
Report Number
Standard
305987
+
305985
IEC61347-1, 2nd Edition, 2012
EN61347-1, 2nd Edition 2013
IEC61347-2-13, 2nd Edition, 2014
EN61347-2-13, 2014
305984-1 + 305984-1 IEC/EN62384, 1st Edition, 2009
LCS1606201548R RoHS-2011/65/EU + AM-2015/863
continued on next page
REV.: 0/2016
www.recom-power.com