English
Language : 

CS10.481 Datasheet, PDF (9/26 Pages) PULS GmbH – 48V, 5A, SINGLE PHASE INPUT
C-Line
CS10.481
48V, 5A, SINGLE PHASE INPUT
7. HOLD-UP TIME
Hold-up Time
typ.
min.
typ.
min.
typ.
min.
AC 100V
62ms
50ms
23ms
19ms
17ms
14ms
AC 120V
107ms
86ms
46ms
37ms
35ms
28ms
AC 230V
103ms
83ms
47ms
38ms
37ms
30ms
at 48V, 2.5A, see Fig. 7-1
at 48V, 2.5A, see Fig. 7-1
at 48V, 5A, see Fig. 7-1
at 48V, 5A, see Fig. 7-1
at 48V, 6A, see Fig. 7-1
at 48V, 6A, see Fig. 7-1
Fig. 7-1 Hold-up time vs. input voltage
Fig. 7-2 Shut-down behavior, definitions
Hold-up Time
a) 48V 2.5A typ.
120ms
a b) 48V 2.5A min.
a
b c) 48V 5A typ.
100
d) 48V 5A min.
e) 48V 6A min.
b
80
60
c
d
40
e
20
0
85 100 120
c
d
e
Input Voltage
180 230Vac
Input
Voltage
Output
Voltage
Zero Transition
Hold-up Time
- 5%
Note: At no load, the hold-up time can be up to several seconds. The green DC-OK lamp is on during this time.
Jul. 2015 / Rev. 2.0 DS-CS10.481-EN
All parameters are specified at 48V, 5A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
9/26