QS20.361 Datasheet, PDF (8/25 Pages) PULS GmbH – 36V, 13.3A, SINGLE PHASE INPUT
Q-Series
QS20.361
36V, 13.3A, SINGLE PHASE INPUT
7. HOLD-UP TIME
Hold-up Time
AC 100V
AC 120V
AC 230V
typ.
64ms
64ms
99ms
at 36V, 6.7A, see Fig. 7-1
typ.
32ms
32ms
51ms
at 36V, 13.3A, see Fig. 7-1
Fig. 7-1 Hold-up time vs. input voltage
100ms
Hold-up
Time
90
80
70
60
50
40
30
20
10
85 120
3366VV, 6, .67.A7A, t,ymp.in.
36V, 13.3A, typ.
36V, 13.3A, min.
Input Voltage
155 190 230Vac
Fig. 7-2 Shut-down behavior, definitions
Input
Voltage
Zero Transition
Output
Voltage
Hold-up Time
- 5%
8. DC-OK RELAY CONTACT
This feature monitors the output voltage, which is produced by the power supply itself. It is independent of a back-fed
voltage from a unit connected in parallel to the power supply output.
Contact closes
Contact opens
Contact re-closes
Contact ratings
Isolation voltage
As soon as the output voltage reaches the adjusted output voltage level.
As soon as the output voltage dips more than 10% below the adjusted output voltage.
Short dips will be extended to a signal length of 250ms. Dips shorter than 1ms will be ignored.
As soon as the output voltage exceeds 90% of the adjusted voltage.
max 60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A resistive load
min 1mA at 5Vdc
min. permissible load
See dielectric strength table in section 18.
Fig. 8-1 DC-ok relay contact behavior
VOUT = VADJ
10%
0.9* VADJ
<
>
1ms
1ms
250ms
open
closed
open
closed
Note: The DC-ok feature requires that the output voltage reaches the nominal (=adjusted) level after turn-on in order to function according
to specification. If this level cannot be achieved, the overload lamp will be on and the DC-ok contact will be open. The overload signal
will only shut off as soon as the adjusted voltage is reached. This is an important condition to consider particularly, if the load is a
battery, the power supply is used in parallel or the power supply is used for N+1 redundant systems.
Oct. 2013 / Rev. 2.2 DS-QS20.361-EN
All parameters are specified at 36V, 13.3A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.