English
Language : 

CT5.121 Datasheet, PDF (8/21 Pages) PULS GmbH – 12V, 8A, TWO-PHASE INPUT
C-Series
CT5.121
12V, 8A, TWO-PHASE INPUT
8. EFFICIENCY AND POWER LOSSES
AC 400V
AC 480V
Efficiency
typ.
85.4%
85.8% at 12V, 8A
Average efficiency *)
typ.
84.7%
84.1%
25% at 2A, 25% at 4A, 25% at 6A. 25% at 8A
Power losses
typ.
1.5W
1.6W
at 0A
8.4W
9.1W
at 12V, 4A
typ.
16.4W
15.9W at 12V, 8A
*) The average efficiency is an assumption for a typical application where the power supply is loaded with 25% of the nominal load for 25%
of the time, 50% of the nominal load for another 25% of the time, 75% of the nominal load for another 25% of the time and with 100%
of the nominal load for the rest of the time.
Fig. 8-1 Efficiency vs. output current at 12V,
typ.
Efficiency
87%
86
85
400Vac
84
480Vac
83
82
81
Output Current
1 2 3 4 5 6 7 8A
Fig. 8-3 Efficiency vs. input voltage at 12V,
8A, typ.
Efficiency
87%
86.5
86.0
85.5
85.0
84.5
84.0
320
Input Voltage Vac
360 400 440 480
520 560
Fig. 8-2 Losses vs. output current at 12V,
typ.
Power Losses
18W
15
400Vac
12
480Vac
9
6
3
Output Current
0
0 1 2 3 4 5 6 7 8A
Fig. 8-4 Losses vs. input voltage at 12V, 8A,
typ.
Power Losses
18W
15
12
9
6
3
o
320
Input Voltage Vac
360 400 440 480
520 560
Jan. 2010 / Rev. 1.0 DS-CT5.121-EN
All parameters are specified at 12V, 8A, 400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
8/21