23. APPLICATION NOTES
23.1. PEAK CURRENT CAPABILITY
Solenoids, contactors and pneumatic modules often have a steady state coil and a pick-up coil. The inrush current
demand of the pick-up coil is several times higher than the steady-state current and usually exceeds the nominal
output current (including the PowerBoost) The same situation applies, when starting a capacitive load.
Branch circuits are often protected with circuit breakers or fuses. In case of a short or an overload in the branch circuit,
the fuse needs a certain amount of over-current to trip or to blow. The peak current capability ensures the safe
operation of subsequent circuit breakers.
Assuming the input voltage is turned on before such an event, the built-in large sized output capacitors inside the
power supply can deliver extra current. Discharging this capacitor causes a voltage dip on the output. The following
two examples show typical voltage dips:
Fig. 23-1 Peak load 16A for 50ms, typ.
12V
Output
Voltage
7V
16A
Output
Current
0A
10ms/DIV
Peak load 16A (resistive load) for 50ms
Output voltage dips from 12V to 7V.
Fig. 23-2 Peak load 40A for 5ms, typ.
12V
Output
Voltage
40A
Output
Current
3.7V
0A
1ms/DIV
Peak load 40A (resistive load) for 5ms
Output voltage dips from 12V to 3.7V.
23.2. BACK-FEEDING LOADS
Loads such as decelerating motors and inductors can feed voltage back to the power supply. This feature is also called
return voltage immunity or resistance against Back- E.M.F. (Electro Magnetic Force).
This power supply is resistant and does not show malfunctioning when a load feeds back voltage to the power supply.
It does not matter, whether the power supply is on or off.
The maximum allowed feed-back-voltage is 25Vdc. The absorbing energy can be calculated according to the built-in
large sized output capacitance which is specified in chapter 6.